  BA_084_2019-05_10.00  Temperature transmitter clamp-on 

Page 4/20 

 

3.1.2 

Mounting the measuring insert 

The mounting procedure for the measuring insert is identical for all clamping elements. 

First apply heat conductive paste to the tip of the measuring insert. Heat conductive paste 
is mandatory for this type series for a good measuring accuracy. 

Now  insert  the  measuring  insert  into  the  bore  in  the  clamping  element.  You  can  position 
the insert in two ways. Choose the position that simplifies the later cable routing. 

Finally tighten the connection by turning the screw connection (see figure 3). No tools are 
required for this step. Never try to turn the housing, if you have a device with field housing 
or integrated transmitter. You might destroy the device by this. 

Do  not  turn  or  move  the  clamping  element  with  a  mounted  measuring  insert.  You  might 
damage or destroy the insert. 

  

 

Figure 3:  Mounting steps for the measuring insert 

  

3.2  Mount / Dismount Display 

In  order  to  dismount  the  display,  turn  off  the  device  cover  and  pull  out  the  display.  The 
three small studs at the outer diameter of the display (all 120°) facilitate removal. 

The display cable can be disconnected either at the display or at the clamp module. When 
reconnecting  the  cable,  please  take  polarity  (red  lead)  into  account.  Otherwise  the  cable 
will not fit into the plug. 

When mounting the display, you can choose its orientation. Complete the process by firmly 
reattaching the cover. 

  

Содержание GV4610 Series

Страница 1: ...eneral Safety Notes 2 1 2 Intended Use 2 1 3 Conformity with EU Regulations 2 2 Transportation and Storage 2 3 Installation and Commissioning 2 3 1 Mechanical Installation 2 3 2 Mount Dismount Display...

Страница 2: ...ice certifies its compliance with the applicable EU Directives for placing products on the market within the European Union You find the complete EU Declaration of Conformity document no KE_052 at www...

Страница 3: ...right Mount the clamping block with the included screws at the intended position on the pipe Do not exceed the allowed tightening torque of 2 Nm for pipe diameters up to 17 2 mm and 4 Nm for bigger p...

Страница 4: ...this step Never try to turn the housing if you have a device with field housing or integrated transmitter You might destroy the device by this Do not turn or move the clamping element with a mounted...

Страница 5: ...al block completely downwards before inserting the cable Otherwise it is not possible to ensure a safe electrical connection Do not forget to tighten the cable gland after the electrical connection is...

Страница 6: ...nsert and pipe For further details please consult the separate calibration guideline for the Clamp on family TA_008 4 2 Maintenance Service When properly installed in accordance with applicable specif...

Страница 7: ...on of the device The gen eral functionality of the buttons is identical in all operating modes Figure 5 Control elements If you press and hold the up or down button it will automatically be triggered...

Страница 8: ...value is larger than the displayable number due to setting a fixed decimal point or an inappropriate unit the largest displayable number is shown flashing In this case please select a different settin...

Страница 9: ...ext Write protection in combination with the lock icon Use the same key combination to unlock the menue again 6 2 3 Icons indicating device status In the top right corner of the display depending on t...

Страница 10: ...ain value is shown at the maxi mum size best readability from a dis tance One additional value can also be shown Table 4 Display layouts You can define what information shall be shown in the layout s...

Страница 11: ...by pressing and holding the ESC button for at least one second Figure 7 Navigating the operating menue In long menues and selection lists a scroll bar on the left side shows the position of the curren...

Страница 12: ...ou cancel the entry and go back to view mode The se lected value is not saved With the OK button the selected value is saved Saving the value is confirmed with an in formation window and the new value...

Страница 13: ...it is reached The value is then set to the parameter limit You can set negative numbers by decreasing the value below zero When you press the ESC button you can cancel the entry at any time and return...

Страница 14: ...Quick Setup basic configuration options are combined to make it possible to quickly configure key functions All functions of the quick setup can also be found at another posi tion in the menue tree T...

Страница 15: ...ld be performed as close as possible to the lower range value and upper range value of the measurement ranges 6 4 3 2 Current adjustment You can use the current adjustment if the reading at the end of...

Страница 16: ...are only meant for your orientation The device uses conversion values with ten decimal places Temperature unit The unit in which the temperature is to be shown can be selected from the following list...

Страница 17: ...inverse 6 4 5 2 Setting the measurement range You can freely set the lower and upper range value within the nominal range of the device Please note that when the turndown is increased the measurement...

Страница 18: ...sponds with the short address which is used for the HART Communication It can be set within a range of 0 to 63 Please note that setting the short address between 1 and 63 will not automatically activa...

Страница 19: ...es capital letters and special characters For the selection the characters are arranged in the order shown below From the end of the list special character you are automatically guided back to the sta...

Страница 20: ...BA_084_2019 05_10 00 Temperature transmitter clamp on Page 20 20 6 4 10 Overview with menue tree and device functions...

Отзывы: