SandSET-1000 12 VDC Sludge Alarm Device  

 

                                 D15649_E-2 

Installation and Operating Instructions 

 

Copyright © 2019 Labkotec Oy 

7/13 

We reserve the right for changes without notice 

TEST FUNCTION 

Test function provides an artificial alarm, which can be used to test the 
function of the SandSET-1000 12 VDC alarm device and the function 
of other equipment, which are connected to SandSET-1000 12 VDC via 
its relays. 

Attention! Before pressing the Test button, make sure that the change 
of relay status does not cause hazards elsewhere! 

 

Normal situation 

When pressing the Test push button: 

 

 

 

Alarm and Fault LED indicators are immediately on. 

 

Buzzer is immediately on. 

 

Relays de-energize after 2 sec of continuous pressing. 

 

 

 

When the Test push button is released: 

 

 

 

LED indicators and buzzer go immediately off. 

 

Relays energize immediately. 

 

 

Alarm on 

When pressing the Test push button: 

 

 

 

Fault LED indicator is immediately on. 

 

Alarm LED indicator remains on. 

 

Buzzer remains on. If it has been reset earlier, it will return to be on. 

 

If relay 1 was already reset, it will de-energize again after 2 sec. of 
continuous pressing. 

 

Test will not affect relay 2, because it is already in alarm status. 

 

 

 

When the Test push button is released: 

 

 

 

The device returns without delay to the preceding status. 

 

 

Fault alarm on 

When pressing the Test push button: 

 

 

 

The device does not react to the test at all. 

3.2 

Factory settings 

If  the  operation  of  SandSET-1000  12  VDC  is  not  as  described  in  the 
previous  chapter,  check  that  the  device  settings  are  as  in  figure  7. 
Change the settings according to the following instructions if needed.  

The  following  tasks  must  only  be  executed  by  a  person  with  proper 
education and knowledge of Ex-i devices. 

We recommend, that when altering the settings the mains voltage is off 
or the device is initialized before the installation is executed. 

 

Figure 7. Factory settings 

The  settings  are  made  with  switches  (MODE  and  DELAY)  and 
potentiometer (SENSITIVITY) located in the upper printed circuit board, 
and  the  jumper  located  in  the  lower  board  (figure  7).  In  figure  7,  the 

Содержание SandSET-1000 12 VDC

Страница 1: ...29 006 260 Fax 358 29 006 1260 28 8 2019 E mail info labkotec fi D15649_E 2 Internet www labkotec fi 1 13 Copyright 2019 Labkotec Oy We reserve the right for changes without notice SandSET 1000 12 VDC...

Страница 2: ...ntrol unit 4 2 2 SET S2 sensor 5 2 3 Cable joint 5 3 OPERATION AND SETTINGS 6 3 1 Operation 6 3 2 Factory settings 7 4 TROUBLE SHOOTING 8 5 REPAIR AND SERVICE 9 6 SAFETY INSTRUCTIONS 9 7 TECHNICAL DAT...

Страница 3: ...t SET S2 sensor junction box and installation supplies Figure 1 Sand separator alarm application SET S2 sensor is installed in the separator or tank and it gives an alarm when the sludge reaches the s...

Страница 4: ...nclosure beneath the mounting holes of the front cover The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must...

Страница 5: ...installation conduit equipped with a inch inner thread Variations in the water level in the well or basin must be taken into account during installation A false alarm results if the sensor is left han...

Страница 6: ...totally immersed in water Mains LED indicator is on Other LED indicators are off Relays 1 and 2 are energized Alarm The two heads of the SET S2 sensor are immersed in sludge or sand Mains LED indicato...

Страница 7: ...remains on Buzzer remains on If it has been reset earlier it will return to be on If relay 1 was already reset it will de energize again after 2 sec of continuous pressing Test will not affect relay 2...

Страница 8: ...ure 7 To do 1 Lift the sensor up in the air or immerse it into sludge and wait 10 seconds 2 Turn the SENSITIVITY potentiometer slowly anticlockwise until the sensor gives an alarm 3 Immerse the sensor...

Страница 9: ...2 3 Any other repair and service works on the device may be carried out only by a person who has received training in Ex i devices and is authorized by the manufacturer In case of queries please cont...

Страница 10: ...9 Due to non linear characteristics of the sensor voltage the interaction of both capacitance and inductance must be taken into account The table below indicates the connecting values in explosion gro...

Страница 11: ...8 DECLARATION OF COMFORMITY...

Страница 12: ...9 DECLARATION OF COMFORMITY...

Страница 13: ...10 DECLARATION OF CONFORMITY...

Отзывы: