SandSET-1000 12 VDC Sludge Alarm Device  

 

                                 D15649_E-2 

Installation and Operating Instructions 

 

Copyright © 2019 Labkotec Oy 

8/13 

We reserve the right for changes without notice 

switches are as set in the factory. 

 

Switch S2 is used to set the 

operational delay of the control unit

When the switch is in low position, relays operate and buzzer is on after 5 seconds after the 
sensor current has reached the trigger level, and if the level still remains on the same side of 
the trigger level. 

When the switch is in high position, the delay is 30 seconds. 

Delays are operational in both directions (energizing, de-energizing). Alarm LED follows the 
sensor  current  value  and  trigger  level  without  delay.  Fault  alarm  takes  place  after  a  fixed 
delay of 5 sec.

 

TROUBLE-SHOOTING 

Problem:  MAINS LED indicator is off 

Possible reason: 

Supply voltage is too low or the fuse is blown. Transformer or MAINS LED 
indicator is faulty. 

To do: 

1. Check if the two pole mains switch is off. 

 

2. Check the fuse. 

 

3. Measure the voltage between poles - and +. It should be 11-17 VDC. 

 

 

Problem:  No alarm when sensor in sludge or air, or the alarm will not go off 

Possible reason: 

The SENSITIVITY setting is wrong in the control unit (see figure 7). 

To do: 

1. Lift the sensor up in the air or immerse it into sludge and wait 10 seconds. 

 

2. Turn the SENSITIVITY potentiometer slowly anticlockwise until the sensor gives 
an alarm. 

 

3. Immerse the sensor into water and wait until the alarm goes off. If the alarm 
does not go off, turn the potentiometer slowly clockwise until the alarm goes off. 

 

4. Lift the sensor up in the air or sink into sludge. The sensor should give an alarm 
again. 

 

 

Problem:  FAULT LED indicator is on 

Possible reason: 

Current in sensor circuit too low (cable break) or too high (cable in short circuit). 
The sensor might also be broken. 

To do: 

1. Make sure, that the sensor cable has been connected correctly to the 
SandSET-1000 12 VDC control unit. See instructions from chapter 2 or SET/S2 
installation and Operating Instructions. 

 

2. Measure the voltage separately between the poles 10 and 11. The voltages 
should be between 10,3….11,8 V. 

 

3. If the voltage is correct, measure the sensor current. Do as follows: 

 

   3.1   Disconnect sensor

’s [+] wire from sensor connector (pole 10). 

 

   3.2   Measure short circuit current between [+] and [-] poles. 

 

   3.3   Connect mA-meter as in figure 8. 

 

   3.4   Connect the wire back to the connector. 

 

 

 

If the problem can not be solved with the above instructions, please contact 
Labkotec 

Oy’s local distributor or Labkotec Oy’s service. 

 

Attention! If the sensor is located in an explosive atmosphere, the multimeter must 
be Exi-approved! 

 
 

 

Содержание SandSET-1000 12 VDC

Страница 1: ...29 006 260 Fax 358 29 006 1260 28 8 2019 E mail info labkotec fi D15649_E 2 Internet www labkotec fi 1 13 Copyright 2019 Labkotec Oy We reserve the right for changes without notice SandSET 1000 12 VDC...

Страница 2: ...ntrol unit 4 2 2 SET S2 sensor 5 2 3 Cable joint 5 3 OPERATION AND SETTINGS 6 3 1 Operation 6 3 2 Factory settings 7 4 TROUBLE SHOOTING 8 5 REPAIR AND SERVICE 9 6 SAFETY INSTRUCTIONS 9 7 TECHNICAL DAT...

Страница 3: ...t SET S2 sensor junction box and installation supplies Figure 1 Sand separator alarm application SET S2 sensor is installed in the separator or tank and it gives an alarm when the sludge reaches the s...

Страница 4: ...nclosure beneath the mounting holes of the front cover The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must...

Страница 5: ...installation conduit equipped with a inch inner thread Variations in the water level in the well or basin must be taken into account during installation A false alarm results if the sensor is left han...

Страница 6: ...totally immersed in water Mains LED indicator is on Other LED indicators are off Relays 1 and 2 are energized Alarm The two heads of the SET S2 sensor are immersed in sludge or sand Mains LED indicato...

Страница 7: ...remains on Buzzer remains on If it has been reset earlier it will return to be on If relay 1 was already reset it will de energize again after 2 sec of continuous pressing Test will not affect relay 2...

Страница 8: ...ure 7 To do 1 Lift the sensor up in the air or immerse it into sludge and wait 10 seconds 2 Turn the SENSITIVITY potentiometer slowly anticlockwise until the sensor gives an alarm 3 Immerse the sensor...

Страница 9: ...2 3 Any other repair and service works on the device may be carried out only by a person who has received training in Ex i devices and is authorized by the manufacturer In case of queries please cont...

Страница 10: ...9 Due to non linear characteristics of the sensor voltage the interaction of both capacitance and inductance must be taken into account The table below indicates the connecting values in explosion gro...

Страница 11: ...8 DECLARATION OF COMFORMITY...

Страница 12: ...9 DECLARATION OF COMFORMITY...

Страница 13: ...10 DECLARATION OF CONFORMITY...

Отзывы: