SandSET-1000 12 VDC Sludge Alarm Device  

 

                                 D15649_E-2 

Installation and Operating Instructions 

 

Copyright © 2019 Labkotec Oy 

10/13 

We reserve the right for changes without notice 

TECHNICAL DATA 

 

SandSET-1000 12 VDC control unit 

Dimensions 

175 mm x 125 mm x 75 mm (L x H x D) 

Enclosure 

IP 65, material polycarbonate 

Ambient temperature 

-

25 ºC…+50 ºC 

Supply voltage 

11-17 VDC 
Fuse 5 x 20 mm 315 mAT (IEC/EN 
60127-2/3) 
The device is not equipped with a mains 
switch 

Power consumption 

Max. 1,2 VA. 
Typical (no alarms) 0.9. VA. 

Sensors 

One Labkotec SET sensor (SET/S2) 

Max. resistance of the 
current loop between the 
control unit and a sensor

 

75

 Ω

Relay outputs 

Two potential-free relay outputs 
250 V, 5 A, 100 VA 
Operational delay 5 sec or 30 sec. 
Relays de-energize at trigger point. 
Operation mode selectable for increasing 
or decreasing level.  

Electrical safety 

IEC/EN 61010-1, Class II  

 , CAT II / 

III 

Insulation level 
Sensor / Mains supply 
voltage 

375V (IEC/EN 60079-1) 

EMC 

Emission 
Immunity 

 
IEC/EN 61000-6-3 
IEC/EN 61000-6-2 

Ex-classification 

 

Special conditions (X) 

ATEX 

IECEx 

       II (1) G    [Ex ia] IIC 
 
(Ta = -25 

C…+50 

C) 

VTT 04 ATEX 031X 
IECEx VTT 10.0003X 

Electrical parameters 
 
 
Characteristic curve of the 
output voltage is trapezoidal 
 
See table 2. 

Um = 23 V          U

o  

= 14,7 V 

I

o  

= 55 mA          P

o  

= 297 mW        

R = 404 Ω 

Manufacturing year: 
Please see the serial number 
on the type plate 

xxx x xxxxx xx YY x 
where YY = manufacturing year 
(e.g. 19 = 2019) 

 
Due to non-linear characteristics of the sensor voltage, the interaction of 
both, capacitance and inductance, must be taken into account. The 
table below indicates the connecting values in explosion groups IIC and 
IIB. In explosion group IIA  the values of the group IIB can be applied. 
 

Max. permissible value 

Combined Co and Lo 

 

Co 

Lo 

Co 

Lo 

II C 

 608nF 

 10 mH 

568nF 
458 nF 
388 nF 
328 nF 
258 nF 

0,15 mH 
0,5 mH 
1,0 mH 
2,0 mH 
5,0 mH 

II B 

3,84μF 

30 mH 

3,5 µF 
3,1 µF 
2,4 µF 
1,9 µF 
1,6 µF 

0,15 mH 
0,5 mH 
1,0 mH 
2,0 mH 
5,0 mH 

L

o

/R

o

 

= 116,5 µH/Ω (IIC) and 466 µH/Ω (IIB) 

 

 

Table 2. SandSET-1000 12 VDC electrical parameters 

 
 
 

 
 
 
 
 

SET/S2 sensor 

Principle of operation 

Ultrasonic 

Enclosure 

IP68 
Materials: PP, PVC, AISI 304, AISI 316 
and NBR rubber 

Ambient temperature 

ºC…+60 ºC 

Supply voltage 

Approx. 12 VDC from SET control unit 

Cable 

Fixed oil resistant PVC cable 3 x 0,5 mm

2

standard length 5 m. 

Weight 

Approx. 450 g 

EMC 

Emission 
Immunity 

 
IEC/EN 61000-6-3 
IEC/EN 61000-6-2 

Ex-classification 
 

ATEX 

IECEx 

       II 1 G   Ex ia IIB T5 Ga 
 
VTT 07 ATEX 0051X 
IECEx VTT 10.0002X 

Electrical parameters 

U

= 16 V            I

i  

= 80 mA 

P

i

 = 320 mW     C

= 3 nF 

L

i  

= 80 

μH         

Manufacturing year: 
Please see the serial 
number on the type plate 

xxx x xxxxx xx YY x 
where YY = manufacturing year 
(e.g. 19 = 2019) 

 

Special conditions concerning Ex-classification (X): 

-  Ambient temperature -25 

ºC…+60 ºC 

-  Shielded sensor cable and extra wires shall be connected to 

equipotential ground 

-  If sensor cable have to be extended, please use LJB2-78-83 or 

LJB3-78-83 junction box. The junction box shall also be 
connected to equipotential ground. 

 

 

 
 
 
 

Figure 9. Dimensional drawing of SET/S2 sensor 

Содержание SandSET-1000 12 VDC

Страница 1: ...29 006 260 Fax 358 29 006 1260 28 8 2019 E mail info labkotec fi D15649_E 2 Internet www labkotec fi 1 13 Copyright 2019 Labkotec Oy We reserve the right for changes without notice SandSET 1000 12 VDC...

Страница 2: ...ntrol unit 4 2 2 SET S2 sensor 5 2 3 Cable joint 5 3 OPERATION AND SETTINGS 6 3 1 Operation 6 3 2 Factory settings 7 4 TROUBLE SHOOTING 8 5 REPAIR AND SERVICE 9 6 SAFETY INSTRUCTIONS 9 7 TECHNICAL DAT...

Страница 3: ...t SET S2 sensor junction box and installation supplies Figure 1 Sand separator alarm application SET S2 sensor is installed in the separator or tank and it gives an alarm when the sludge reaches the s...

Страница 4: ...nclosure beneath the mounting holes of the front cover The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must...

Страница 5: ...installation conduit equipped with a inch inner thread Variations in the water level in the well or basin must be taken into account during installation A false alarm results if the sensor is left han...

Страница 6: ...totally immersed in water Mains LED indicator is on Other LED indicators are off Relays 1 and 2 are energized Alarm The two heads of the SET S2 sensor are immersed in sludge or sand Mains LED indicato...

Страница 7: ...remains on Buzzer remains on If it has been reset earlier it will return to be on If relay 1 was already reset it will de energize again after 2 sec of continuous pressing Test will not affect relay 2...

Страница 8: ...ure 7 To do 1 Lift the sensor up in the air or immerse it into sludge and wait 10 seconds 2 Turn the SENSITIVITY potentiometer slowly anticlockwise until the sensor gives an alarm 3 Immerse the sensor...

Страница 9: ...2 3 Any other repair and service works on the device may be carried out only by a person who has received training in Ex i devices and is authorized by the manufacturer In case of queries please cont...

Страница 10: ...9 Due to non linear characteristics of the sensor voltage the interaction of both capacitance and inductance must be taken into account The table below indicates the connecting values in explosion gro...

Страница 11: ...8 DECLARATION OF COMFORMITY...

Страница 12: ...9 DECLARATION OF COMFORMITY...

Страница 13: ...10 DECLARATION OF CONFORMITY...

Отзывы: