background image

Page 4

 

LAARS Heating Systems

1.8  Jacket (normally fitted)

If not fitted, assemble panels in accordance with 

in struc tions  in  Figure  4.

1.9  Oil Burner (normally fitted)

If not fitted, insert burner tube into boiler so 

that it is ap prox i mate ly ¼" (6mm) from inside wall of 
ceraform chamber, then clamp mounting flange and 
bolt up to front-plate (see Figure 3).

The burner should be wired and connected to 

the oil line in accordance with the manufacturer’s 
instructions.

1.10  Installation of Alternate Nozzles for        

  Higher Output

This operation shall only be carried out by a 

trained and licensed Service Technician in accordance 
with the burner manufacturer’s instructions included in 
the literature package provided with this boiler. 

1.11  Boiler Controls (normally fitted)

If controls are supplied separately, fit them to the 

boiler in the positions shown in Figure 3, with jacket 
in place.

Circulator - 1¼" return tapping at front of boiler.
Tridicator - temp/press. gauge.
Relief Valve - Provide ¾" tee and auto vent as 

shown on front page for air elimination.

Aquastat Relay - L8124A or L7224A - ¾" 

tapping in coil plate.

Fit a drain valve (not supplied) in a tee at 

hy dron ic return connection and check all connections 
are made wa ter tight.

1.12  Oil

USE ONLY No. 2 HEATING OIL. Do not use 

gasoline, crankcase draining or any oil con tain ing 
gasoline.

1.13  Oil Storage and Pipe Layout

Storage Tank: 

Consult local fire and building   

codes for acceptable fuel storage methods in your area.

Fuel Line:

 A single pipe system of not less 

than 3/8" OD copper tubing is recommended when 
fuel storage level is not below the fuel unit. A two 
pipe system of not less than 3/8" OD copper tubing is 
recommended when lowest fuel level is below but not 
more than 8 feet below fuel unit.

Important:

 Refer to burner (pump) instructions 

for detailed fuel line and pump usage information. All 
installations must conform to local and national codes.

See Figures 5A and 5B.
Figure 5A One-pipe system - pipe and tank 

layout.

Figure 5B Two-pipe system - pipe and tank 

layout.

1.14  Electrical Wiring

All wiring must comply with the National 

Electrical Code, NFPA 70, local codes and ordinances 
regarding wire size, type of insulation and enclosures 
etc. (see Figure 6).

1.15  Operation  (Honeywell L8124A or   

  L7224A aquastat relay)

A call for heat from the room thermostat causes 

the re lay to “make “ the burner circuit and also feed 
the cir cu la tor provided the boiler water tem per a ture  is 
above the low limit setting (usually 190°F [88°C] to 
210°F [99°C]). The burner and cir cu la tor  then  continue 
to run until the room thermostat is satisfied.

A high limit switch shuts off burner in the event 

of water temperature exceeding the high limit setting, 
usually 20°F (-7°C) to 30°F (-1°C) above the low limit 
setting.

The low limit switch and circulator maintain 

boiler water temperature for domestic hot water 
ser vic es  and  pre vent circulation of heating system 
water if domestic water is not hot enough.

1.16  Domestic Water Piping

1.      Connect anti scald tempering valve (12) “HOT” 

port to hot water outlet from unit. This valve 
should be mounted 3" (76mm) to 6" (152mm) 
below the outlet and set for 120° F mixed 
delivery temperature or as local codes dictate 
(see Figure 1).

2.      Connect gate or shutoff valve (13) to anti scald 

tempering valve (12) “MIX” port, and another to 
the cold water inlet.

3.      Connect pressure relief valve (11) (if required

by codes), maximum 150 PSI as close to the unit 
as possible. No other valves or restrictions may 
be installed between the DHW coil and the
relief valve.
(DO  NOT  USE  A  TEM PER A TURE/PRES SURE 

RELIEF VALVE AS THIS IS NOT A STOR AGE 
HOT WATER HEATER).

B

O

I

L

E

R

11

12

13

3 - 6"

(76mm - 152mm)

Figure 1. Domestic water piping.

OUT OF

PRODUCTION

Содержание newport

Страница 1: ...ich could cause serious injury property damage or death Improper installation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explos...

Страница 2: ...er normally fitted 4 1 10 Installation of Alternate Nozzles for Higher Output 4 1 11 Boiler Controls normally fitted 3 1 12 Oil 3 1 13 Oil Storage and Pipe Layout 3 1 14 Electrical Wiring 4 1 15 Opera...

Страница 3: ...gnee 1 3 Boiler Location The boiler should be positioned as near to the chimney as possible and have a minimum smoke pipe connector length of 18 457mm CAUTION Newport boilers must not be directly conn...

Страница 4: ...unit Important Refer to burner pump instructions for detailed fuel line and pump usage information All installations must conform to local and national codes See Figures 5A and 5B Figure 5A One pipe...

Страница 5: ...tire flue and venting system inspected 1 17 Cleaning the Boiler To maintain the high thermal efficiency and a long life from your boiler it should be cleaned at least once a year preferably at the end...

Страница 6: ...be causing a blockage 1 19 Servicing the Burner This should only be carried out by a trained and licensed service technician in accordance with the burner maker s instructions 1 20 Maintenance of the...

Страница 7: ...35 133 30 150 44 160 47 177 52 Output MBTU hr kW 90 26 105 30 116 34 130 38 139 40 154 48 Efficiency AFUE 83 6 83 1 83 1 83 7 83 0 83 0 Net Stack Temperature F C 312 156 353 178 371 188 351 177 386 1...

Страница 8: ...front panel 3 with screws 2 Slide assembled jacket over boiler and secure side panels to base tray 3 Fix rear panel 4 to sides 4 Adjust corner brackets 5 on heat exchanger so they touch inside of jack...

Страница 9: ...rmation Air vent Fill pipe Valve Figure 5A 1 min Oil tank H Filter P Burner Boiler Air vent 1 min Fill pipe Oil tank Figure 5B Valve Filter Burner Boiler H PIPE LENGTHS H One Pipe Gravity System 3 8 O...

Страница 10: ...verload protection as required 24V Room Thermostat 1K L1 Hot Power Supply 120V L2 Circulator Switch Low Limit Circulator Hi Limit 1K2 Oil Burner Relay Heating Circulator AQUASTAT RELAY L8124A 1K1 WIRI...

Страница 11: ...85 110 Use with P N 51 056 51 090 Flue Cover Assembly 85 110 52 108 Front Panel Assembly 85 110 52 116 Left Panel Assembly 85 110 52 124 Right Panel Assembly 85 110 51 128 Top Panel Assembly 85 110 5...

Страница 12: ...Fax 800 559 1583 Customer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130...

Отзывы: