Model LC (Australia) Pool and Spa Heater
Page 21
5.
Remove the two screws securing the antirotation
bracket to the inner panel, and the three screws
attaching the burner tray. Slide the burner tray
out of the heater (see Fig. 33).
NOTE:
Due to sharp edges on the metal burner, wear
protective gloves for the next steps.
6.
Hold the burner firmly, and push it away from
the manifold until it is clear of the orifice. Slide it
out of the burner tray (see Fig. 34).
7.
To replace the burner, insert the rear into the slot
at the rear of the burner tray, line it up with the
proper orifice and snap it into position.
8.
Reinstall the burner tray by sliding it back into
the heater and securing it with the two brackets.
9.
Reconnect the gas piping, turn on the gas supply
and check the system for leaks using a soap
solution.
10.
Reconnect the electrical wires to the gas valve
and the ignition sensor lead to the ignition module
according to the wiring diagram (see Fig. 5).
Figure 33. Burner Tray Removal
3.
Hold the burner firmly, and push it away from
the manifold until it is clear of the orifice. Slide it
out of the burner tray (see Fig. 34).
4.
To replace the burner, insert the rear into the slot
at the rear of the burner tray, line it up with the
proper orifice and snap it into position.
5.
Install the pilot assembly on the new burner and
install it in the burner tray. Connect a new pilot
gas tube to the pilot assembly and gas valve.
6.
Reinstall the burner tray by sliding it back into
the heater and securing it with the two brackets.
7.
Reconnect the gas piping, turn on the gas supply
and check the system for leaks using a soap
solution.
8.
Reconnect the electrical wires to the gas valve
and the ignition sensor lead to the ignition module
according to the wiring diagram (see Fig. 5).
4E-1. Pilot Burner Removal
1.
Disconnect the pilot gas tube from the gas valve.
2.
Detach the pilot burner assembly from the burner
bracket and remove the burner.
NOTE:
Due to sharp edges on the metal burner, wear
protective gloves for the next steps.
Figure 34. Gas Burner Removal
4F. Heat Exchanger Water Passages
Inspection
Scale can accumulate inside the heat exchanger
tubes. The easiest method of determining the degree of
scale buildup is to periodically inspect the tube having
the highest temperature. This can be done by removing
the drain plug on the right side of the heater (see Fig.
35). Perform this inspection after sixty days of opera-
tion, and after 120 days of operation. This will estab-
lish a regular inspection routine.