background image

Model LC (Australia) Pool and Spa Heater

Page 13

4C. Electrical Troubleshooting

An authorized service technician, qualified in

pool heater maintenance, should do all troubleshooting
and repairing on the LC (Australia) heater. Before
calling a service technician, the heater owner can check
the following:

1. Be sure the system pump is operating and the

filter is clean.

2. The heater circuit breaker and/or disconnect

switch must be ON, and the switch on the heater
control panel must be pointing at one of the tempera-
ture control knobs.

Figure 17. Gas Pressure Test Procedures

TESTING MAIN LINE GAS PRESSURE

1.

Attach the manometer* to the heater jacket.

2.

Open both columns on the manometer.

3.

Use the shut-off valve outside the heater jacket to shut off
all gas supply to the heater.

4.

Remove the cap screw from the gas fitting on the INPUT side
of  the gas valve.

5.

Attach one end of the manometer hose to the fitting on the
gas valve and the other end to the manometer.

6.

Open gas supply valve to the heater and set the thermostat
high enough to call for heat.

7.

Move the rotary switch to POOL or SPA. This should activate
the main burners.

8.

With the main burners firing, the manometer reading should
be between 1.13 and 1.75 kPa  (natural gas) and between
2.5 and 2.75 kPa (propane gas).

9.

Move the rotary switch to OFF and refer to Lighting and
Shutdown label to shut down the system.

10. Disconnect the manometer tubing from the gas valve and

replace screw on the gas fitting.

TESTING MANIFOLD GAS PRESSURE

1.

Attach the manometer* to the heater jacket.

2.

Open both columns on the manometer.

3.

Use the shut-off valve outside the heater jacket to shut off
all gas supply to the heater.

4.

Remove the cap screw from the gas fitting on the OUTPUT
side of  the gas valve.

5.

Attach one end of the manometer hose to the fitting on the gas
valve and the other end to the manometer.

6.

Wait five minutes.

7.

Open gas supply valve to the heater and set the thermostat
high enough to call for heat.

8.

Move the rotary switch to POOL or SPA. This should activate
the main burners.

9.

The manometer reading should be 1.0 kPa for natural gas
and 2.25 kPa  for propane gas.

10. Move the rotary switch to OFF and refer to Lighting and

Shutdown label to shut down the system.

11. Disconnect the manometer tubing from the gas valve and

replace screw on the gas fitting.

*A dry gas pressure gauge may be used for either test.

3. All external manual gas valves must be open,

and the heater's gas valve must be in the ON position.

4C-1. Control System Troubleshooting

Sequence

A. Heater Does Not Come On

IMPORTANT:

 Disconnect power to the heater before

removing or replacing any component or wire connec-
tion. If the power is not disconnected, "jumpering" the
gas valve or accidental grounding of the wire harness
or component terminals to the heater frame or jacket
could cause the fuse to blow.

Содержание Lite 2 LC

Страница 1: ...using property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try...

Страница 2: ...d Shutdown 9 3C 1 Lighting the Heater 9 3C 2 Filter Pump Operation 9 3C 3 Shutdown 9 3D Spring and Autumn Operation 9 3E Winterizing 10 3F Water Chemistry 10 3F 1 For Pool 10 3F 2 For Spa 10 3F 2a Cor...

Страница 3: ...water Section 3F explains proper pool water chemistry SECTION 2 Installation Instructions WARNING Improper installation or maintenance can cause nausea or asphyxiation from carbon monoxide and flue g...

Страница 4: ...e base or on the top Do not locate the heater close to sprinklers the water could damage the controls and the electronics If you are installing the heater under an overhang there must be a minimum cle...

Страница 5: ...00 mm Minimum Front of heater 450 mm Minimum Floor Noncombustible If you are installing the heater on a combustible surface an approved noncombustible base must be installed 305 mm of 305 mm of Figure...

Страница 6: ...2 mm 40 mm 400 32 mm 40 mm 50 mm Install a union on the gas supply line outside the heater jacket including a drip leg and a manual shut off valve see Fig 4 Do not use a restrictive gas cock Before op...

Страница 7: ...r on or off but will not switch between the two temperature controllers on the Flex Temp control panel To connect a 3 wire remote not supplied by Waterpik Technologies order a wire harness assem bly p...

Страница 8: ...ter to operate properly 2J Pressure Switch Adjustment The pool filter must be clean before making this adjustment The heater does not have to be firing 1 Turn the rotary switch to OFF and make sure th...

Страница 9: ...flow rates up to 475 liters per minute L min If the system filter flow rate is higher than 475 L min install a manual bypass valve Figure 9 shows a valve installed between the Figure 10 Thermometer a...

Страница 10: ...rols cannot be calibrated in the field If the control is faulty shut down the heater and replace the control according to the instructions in Section 4 DO NOT use the rotary switch to completely shut...

Страница 11: ...ter back up to the desired tempera ture in the least amount of time In areas subject to only short freeze periods turn off the heater and run the filter pump continuously for the length of the cold pe...

Страница 12: ...pool water between 7 2 and 7 6 3F 2 For Spa The control of proper chemical balance in spa water is more critical than in a swimming pool for satisfactory heater operation Usage density in a spa is ma...

Страница 13: ...g tranquilizers antihistamines or anticoagulants should not use spas or hot tubs 7 Prolonged immersion in hot water can induce hyperthermia Hyperthermia occurs when the internal body temperature reac...

Страница 14: ...egular inspections by authorized personnel at least annually to keep the heater operating efficiently The authorized person shouldcheckthefollowing 1 Keep the top and surrounding area of the heater cl...

Страница 15: ...to Lighting and Shutdown label to shut down the system 10 Disconnect the manometer tubing from the gas valve and replace screw on the gas fitting TESTING MANIFOLD GAS PRESSURE 1 Attachthemanometer tot...

Страница 16: ...Verify that the electrical circuit serving the heater is ON and there is power to the heater 8 Make sure the switch on the heater control panel is pointing at one of the temperature controllers 9 Ver...

Страница 17: ...of an open fusible link is abnormal wind conditions This could be caused by improper clearances to buildings and walls See Section 2B for proper clearances c Wire Harness Limit Switches To test the wh...

Страница 18: ...heater and the switch a Blow out the tube until clear b Fill the siphon loop tube and the switch with heavy non detergent oil SAE 50 preferred using a pump type oil can see Fig 15 c Install the sipho...

Страница 19: ...res and attach the resistor in the same location The heater should operate with the same temperature control knob in the center of the dial If the heater fails to operate replace the temperature contr...

Страница 20: ...26 The following tests determine if the ignition control is operating correctly Keep in mind that the heater has a lockout ignition control See Section 3C Before doing the electrical tests make a vis...

Страница 21: ...t If the pilot flame and sensor electrode are all right but there is no main burner ignition check for voltage between the blue wire on the transformer to 24V on the ignition control and the brown wir...

Страница 22: ...Remove the two screws securing the antirotation bracket to the inner panel and the three screws attaching the manifold bracket Slide the burner tray out of the heater see Fig 33 6 Remove the pilot gas...

Страница 23: ...t the rear into the slot at the rear of the burner tray line it up with the proper orifice and snap it into position 5 Install the pilot assembly on the new burner and install it in the burner tray Co...

Страница 24: ...ation strips are on top of the side panels of the combustion chamber and lower the heat exchanger into place 10 If a header bolt is stripped in the process of reassembly it can be driven out of the he...

Страница 25: ...embly straight up 3 Remove the screw securing the rainshield at the rear of the heater and set it aside 4 Lift off the rainshield and set it aside Inlet Outlet Header Figure 37 Flow Control Assembly D...

Страница 26: ...ader and locate the switch in its original position Carefully straighten the copper tubing as necessary Fasten the tubing to the rear panel using the cable clip and screw 20 Install the temperature se...

Страница 27: ...flue collector and secure it with the screw removed earlier 34 Replace the top assembly Make sure the tabs are outside the heater jacket Secure the top assembly with the hex head screws 35 Replace th...

Страница 28: ...30 32 28 22 76 79 38 36 60 39 34 35 71 68 70 69 72 82 86 81 87 85 29 88 89 90 66 62 66 65 91 20 21 40 67 64 63 80 26 19 24 17 23 16 18 25 53 97 96 51 52 1 2 3 4 5 6 8 7 9 11 15 12 10 14 13 50 59 61 7...

Страница 29: ...er Cord Aii R0107600 VENT SYSTEM 51 Top Enclosure 125 400 R0313201 05 52 Rainshield Kit 125 400 R0318311 15 53 Flue Collector Assembly 125 400 R0316406 10 55 Outdoor Vent Cap 125 400 10561511 15 56 In...

Страница 30: ...57 NOTES 1 The Laars Lite 2 Australia is approved by the Australian Gas Association as a swimming pool heater for both propane and natural gases 2 The Laars Lite 2 Australia is constructed for 516 kPa...

Страница 31: ...Model LC Australia Pool and Spa Heater Page 29 NOTES...

Страница 32: ...nologies shall not exceed the repair or replacement of defective parts by factory authorized technicians and shall not include transportation to or from factory any labor costs and consequential or in...

Страница 33: ...ease omit the last line which reads Adding a flue cap may be necessary Page 3 Section 2C Indoor Installation Introductory paragraph Please make the following change paragraph should read The Laars Lit...

Страница 34: ...with the kit To order a manual reset high limit switch kit contact your local authorized Laarss distributor or call Waterpik Technologies at the telephone number listed on the back of this manual 600...

Отзывы: