Manual
Kuhse Gateway Module
KGM - KEA
HB-KGM-KEA_EN Version 01
Date: 23rd. May 2017
Page 50 of 75
8.1.1
Digital signals KEA2xx
8.1.1.1
Fault messages (FC03)
Register
47001
47002
Bit 15
Fault 8 - e.g. COLLECTIVE FAULT A
Power controller impeded
Bit 14
Fault 7 - e.g. COLLECTIVE FAULT W
Overspeed
Bit 13
Fault 6 - e.g. OVERSPEED
Failed start
Bit 12
Fault 5 - e.g. INADEQUATE COOLANT
Engine does not switch off
Bit 11
Fault 4 - e.g. GEN. OVERTEMP.
Battery undervoltage
Bit 10 Fault 3 - e.g. EMERGENCY STOP PRESSED
Parameterised fault 19
Bit 09
Fault 2 - e.g. COOLANT TEMP. MAX.
Parameterised fault 18
Bit 08 Fault 1 - e.g. INSUFFICIENT OIL PRESSURE
Parameterised fault 17
Bit 07
Parameterised fault 16
Gen. phase sequence
Bit 06
Fault 15 - e.g. MAINS SWITCH
Mains phase sequence
Bit 05
Fault 14 - e.g. LEAKAGE
Gen. Switch instance
Bit 04
Fault 13 - e.g. TANK OVERFILLING
Mains switching event
Bit 03
Fault 12 - e.g. SOOT FILTER BYPASS.
Gen. off impeded
Bit 02
Fault 11 - e.g. STORAGE TANK MIN.
Mains off impeded
Bit 01
Fault 10 - e.g. DAY TANK MIN.
Synchronisation impeded
Bit 00
Fault 9 - e.g. OVERVOLTAGE TRIG.
Reverse power
Faults 1-16 are dependent on the parameterisation of the KEA fault inputs!
Register
47003
47004
Bit 15
Gen. thermal overload
Fault 56
Bit 14
Gen. asymmetric load
Fault 55
Bit 13
Gen. overcurrent II
Fault 54
Bit 12
Gen. overcurrent I
Fault 53
Bit 11
Alarm 36
Fault 52
Bit 10
Alarm 35
Fault 51
Bit 09
Alarm 34
Fault 50
Bit 08
Alarm 33
Fault 49
Bit 07
Gen. overfrequency
Fault 64
Bit 06
Gen. underfrequency
Fault 63
Bit 05
Gen. overvoltage
Fault 62
Bit 04
Gen. undervoltage
Fault 61
Bit 03
Mains overfrequency
Fault 60
Bit 02
Mains underfrequency
Fault 59
Bit 01
Mains overvoltage
Fault 58
Bit 00
Mains undervoltage
Fault 57