7.1.2
Counter values KEA1xx (FC03)
Register Counter values
Dimension
Value
47201 Operating hours MSW
h
65536
47202 Operating hours LSW
h
1
47203 Start counter MSW
-
65536
47204 Start counter LSW
-
1
47205 Reserve MSW
-
65536
47206 Reserve LSW
-
1
47207 Reserve MSW
-
65536
47208 Reserve LSW
-
1
47209 Reserve MSW
-
65536
47210 Reserve LSW
-
1
7.1.3
Commands to KEA 1xx (FC16)
Register Command and parameter
Value
47301
Command #0 : Target value from ZLT
$243C
47302
Parameter #0 : Power specification
In
kW
, without commas
47303
Command #1: n/a
$0000
47304
Parameter #1: n/a
0
47305
Command #2 : Command from ZLT
$2850
47306
Parameter #2 : Bit commands
(Bef. 8…1 / 16…9)
e.g. Central control system (ZLT)
command 1: $0100
47307
n/a
0
47308
n/a
0
47309
n/a
0
47310
n/a
0
47311
n/a
0
47312
n/a
0
47313
n/a
0
47314
n/a
0
47315
n/a
0
47316
n/a
0
To ensure that the commands will be accepted by the KEA, the value cited in the
table for the respective command must be transmitted in the data word.
The transmission of command values that are not stipulated (other than zero) can
result in undesired reactions by the KEA!