Date: 23rd. May 2017
Page 11 of 75
5.2
Relay outputs
4 controllable relay outputs are integrated into the device for potential-free signalling of alarm
messages and for controlling external devices and modules.
The relay outputs are wired as changeover contacts (COM, NC, NO) to the external connection.
"SIG OUT 1-4" connector - relay outputs (isolated, 30 V / 1 A max.)
Pin Function
1
Relay 1 - NC
2
Relay 1 - COM
3
Relay 1 - NO
4
Relay 2 - NC
5
Relay 2 - COM
6
Relay 2 - NO
7
Relay 3 - NC
8
Relay 3 - COM
9
Relay 3 - NO
10
Relay 4 - NC
11
Relay 4 - COM
12
Relay 4 - NO
Connector MC 1.5/12-ST-3.5; Phoenix Contact 1840463; min. 12 x 0.5mm2
In relaxed condition (relay coil not energised) the COM and NC contacts are closed.
In activated condition (relay coil energised) the COM and NO contacts are closed. In addition, this
active condition is indicated separately with a green LED for each relay output (SIG OUT 1-4).
A delay time for the relay reporting can be set in the configuration interface.