Appendix
E 811 GB
28
27/02/2013
7 Appendix
7.1 Technical Data
7.1.1
Basic Data
Function
........................................................ industrial monitor with touch functionality
Design
........................................................... control panel mounting at the front and held by screws at the
back
Dimensions ............................................... see Technical Properties
3.3
Weight ...................................................... see Technical Properties
3.3
Protection ................................................. IP 20 / front IP 65
Environment
Sound emission ............................................. <40dB (A) compliant to DIN 45635-1
Pixel defects .................................................. pixel defect class II (ISO 13406)
Permits ........................................................... CE
Power supply
Supply voltage (DC) ................................
24 VDC / (10 ... 32)
Brief voltage interruption
............................................................. min. 10 ms (at 19.2 V)
recovery min. 1s
Max. power consumption ......................... see Technical Properties
3.3
Electromagnetic compatibility (EMC)
EMC ..........................................................
pursuant to EN 61131-2, sections 8 to 10, zone B
Noise emission ......................................... EN 61000-6-4, -noise emission to industrial environments-
Noise immunity ......................................... EN 61000-6-2, -immunity for industrial environments-
noise voltage conducted by ................
power supply lines ............................... +/- 2 kV compliant to IEC 61000-4-4; burst
+/- 500 V compliant to IEC 61000-4-5; surge, symmetrical
+/- 500 V compliant to IEC 61000-4-5; surge, asymmetrical
signal lines ........................................... +/- 1 kV compliant to IEC 61000-4-4; burst; length > 3 m
static electricity discharge ................... +/- 4 kV contact discharge compliant to IEC 61000-4-2
+/- 8 kV air discharge compliant to IEC 61000-4-2
HF interference .................................... 10 V/m 80 – 1000 MHz, 80% AM compliant to IEC 61000-4-3
3 V 1.4 GHz – 2.0 GHz, to IEC 61000-4-3
1 V 2.0 GHz – 2.7 GHz to IEC 61000-4-3
10 V 150 kHz – 80 MHz, to IEC 61000-4-6
Admissible ambient conditions
Storage and transportation
Temperature ........................................ see Technical Properties
3.3
relative humidity .................................. 5% to 90% at 25°C (non-condensing)
Vibration (not frequent)........................ 5 Hz to 9 Hz: 3.5 mm, 9 Hz to 150 Hz: 9.8 m/s
2
Shock (not frequent) ............................ free fall from 1m height in original packaging
Operation
Ambient temperature ........................... horizontal installation:
0...50 °C
vertical installation: 0 ... 50 °C
relative humidity .................................. control cabinet or mounting space
5% to 90% at 25°C (non-condensing)
front after installation: 100%
Vibration (not frequent)........................ 10 Hz to 58 Hz: 0.075 mm, 58 Hz to 150 Hz: 9.8 m/s
2
Shock (not frequent) ............................ 15g for 11 ms