KFU 2-/4-
215
The parameter
Local/Remote
412
defines the operating behavior and enables a
change between the control via contacts or the control unit and/or the interface.
Local/Remote
412
Function
0 -
Control via Contacts
The Start and Stop commands as well as the direction
of rotation are controlled via digital signals.
1 -
Control via state ma-
chine
The Start and Stop commands as well as the direction
of rotation are controlled via the DRIVECOM State-
machine of the communication interface.
2 -
Control via remote
contacts
The Start and Stop commands as well as the direction
of rotation are controlled via logic signals through the
communication protocol.
3 -
Control via keypad,
dir. of rot. via con-
tacts
The Start and Stop commands are controlled from the
control unit and the direction of rotation is controlled
via digital signals.
4 -
Control via KP or
cont.,
dir. of rot. via con-
tacts
The Start and Stop commands are controlled from the
control unit or via digital signals. The statement of the
direction of rotation only with the help of the digital
signals.
5
-
Control 3-wire, dir. of
rot. via contacts
3-wire; control of direction of rotation and signal
3-wire
control
87
via contacts.
13
-
Control via keypad,
dir. of rot. via keypad
The Start and Stop commands as well as the direction
of rotation are controlled via the control unit.
14
-
Control via KP or
cont.,
dir. of rot. via con-
tacts
The Start and Stop commands are controlled from the
control unit or via digital signals. The statement of the
direction of rotation only with the help of the operating
unit.
20
-
Control via cont.,
clockwise only
The Start and Stop commands are controlled via digital
signals. Fixed direction of rotation, clockwise rotation
only.
23
-
Control via keypad,
clockwise only
The start and stop commands are controlled via key-
pad. Fixed direction of rotation, clockwise rotation only.
24
-
Control via cont. +KP,
clockwise rot. only
The Start and Stop commands are controlled from the
control unit or via digital signals. Fixed direction of rota-
tion, clockwise rotation only.
30 to 34
Operation mode 20 to 24, anticlockwise direction of
rotation only.
43
-
Control via KP,
dir. of rot. via con-
tacts
The start and stop commands are controlled via digital
signals. The statement of the direction of rotation
comes from the operating unit or via digital signals.
44
-
Control via cont.+ KP,
sense of rot. via cont.
+ KP
The Start and Stop commands as well as the sense of
rotation can be controlled from either the control unit
or via digital signals.
46
-
Control via 3-wire +
KP,
dir. of rot. via con-
tacts + KP
3-wire and control unit; control of direction of rotation
and signal
3-wire control
87
via contacts or control
unit.
Note:
If the operation mode is changed while the drive is running, the drive will
not be stopped if no stop command is present in the new operation mode.