KFU 2-/4-
176
14.4.10 Handshake Traverse Function
Via parameter
Handshake Traverse Function
49
, the signal source is selected for
specification of the direction of rotation of the slave drive of the shot-effect function.
The shot-effect function is switched on via parameter
Operation mode
435
.
14.4.11 External error
Parameterization of an external error enables switching off or shutting down several
frequency inverters at a time if a fault occurs in the plant or the drive. If an error oc-
curs in a frequency inverter, the error signal can be transmitted via a bus system and
the required reaction can be triggered in another frequency inverter. Parameter
Ex-
ternal error
183
can be assigned the logic signal or digital input signal which is to
trigger the external error.
Via parameter
Operation mode ext. error
535
, the response to an external error can
be configured.
Operation mode 535
Function
0
-
Disabled
No response to external errors.
1
-
Error-Switch-Off
The drive is switched off and the error message „F1454
External Error“ is output if the logic signal or digital input
signal for parameter
External Error
183
is present.
2 - Shutdown, Error
The drive is stopped at the current deceleration ramp and
the error message „F1454 External Error“ is output if the
logic signal or digital input signal for parameter
External
Error
183
is present.
3
-
Emergency-Stop,
Error
The drive is stopped at the current emergency stop ramp
and the error message „F1454 External Error“ is output if
the logic signal or digital input signal for parameter
Exter-
nal Error
183
is present.