48
Relative
Humidity
0–90% noncondensing
Operating
Altitude
Up to 3,000 meters (9,843 ft) above sea level
Transit Altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible Noise
<55 dBA at 1 meter typical
Leakage
Current
<1.5 mA
Table 20. Battery Runtimes (in Minutes) at 100% Load (ALL Models)
Model
Internal Batteries
+ 1 EBP
+ 2 EBPs
+ 3 EBPs
+ 4 EBPs
1K
3
15
25
40
53
1.5K
3
15
25
40
53
2K
3
15
25
40
53
3K
3
17
31
52
69
NOTE Battery times are approximate and vary depending on the load
configuration and battery charge.
Table 21. Battery
Internal Batteries
EBPs
Battery
Configuration
1000 VA: 24 Vdc (2, 12V, 9 Ah)
1500 VA: 36 Vdc (3, 12V,9 Ah)
2000 VA: 48Vdc (4,12V,9Ah)
3000 VA: 72 Vdc (6 , 12V,9Ah)
1K -EBP: 24 Vdc (2 x 2 ,12V, 9 Ah)
1.5K -EBP: 36 Vdc (2 x 3 ,12V, 9 Ah)
2K -EBP: 48Vdc (2 x 4 ,12V, 9 Ah)
3K -EBP: 72 Vdc (2 x 6 ,12V, 9 Ah)
Fuses
(2) 30A/250 Vdc fuses
(4) 30A/250 Vdc fuses per EBP
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 25°C (77°F)
Monitoring
Advanced monitoring for earlier failure detection and warning
Recharge Time
(to 90%)
Internal batteries: 3 hours 1 EBP: 9 hours; 2 EBPs: 15 hours; 3 EBPs: 21 hours;
4 EBPs: 27 hours
Battery Port
External six-pole Anderson connector on UPS for connection to EBP