7. Press the combination start up buttons on the UPS front cover for at least half a
second. The UPS will start up and the LED will turn on and off sequentially.
0T
8. Check the UPS front cover display for active alarms or notices. Resolve any
active alarms before continuing. See Troubleshooting” on page
49
. If the
indicator is on, do not proceed until all alarms are clear.Check the UPS
status from the front cover to view the active alarms. Correct the alarms and
restart if necessary.
0T
10. Verify that the
indicator illuminates solid, indicating that the UPS is
operating normally and any loads are powered.
0T
11. If optional EBPs are installed, see “Configuring Battery settings” on page
28
to
set the number of installed EBPs.
0T
12. To change any other factory-set defaults, see “User settings” on page
25
.
NOTE
0T
:
At initial startup, the UPS sets system frequency according to input line
frequency (input frequency auto-sensing is enabled by default).
NOTE
0T
:
At initial startup,please set the output voltage needed before start up the
UPS,After the subsequent startup,the UPS will output the setting voltage.
0T
13
.
If you installed an optional EPO, test the EPO function: Activate the external
EPO switch. Verify the status change on the UPS display. Deactivate the
external EPO switch and restart the UPS.
NOTE
0T
:
The internal batteries charge to 80% capacity in less than 5 hours. However,
we recommend that the batteries should be charged for 48 hours after installation
or long-term storage. If optional EBPs are installed, see the recharge times listed in
Table 21 on page
48
.