UPS Maintenance
0T
This section explains how to:
0T
Care for the UPS and batteries
0T
Replace Extended Battery Packs(EBPs)
0T
Test new batteries
0T
Recycle used batteries or UPS
UPS and Battery Care
0T
For the best preventive maintenance, keep the area around the UPS clean and dust‐
free. If the atmosphere is very dusty, clean the outside of the system with a vacuum
cleaner. For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
NOTE
The batteries in the UPS are rated for a 3–5 year service life. The length of
service life varies, depending on the frequency of usage and ambient temperature.
Batteries used beyond expected service life will often have severely reduced
runtimes. Replace batteries at least every 5 years to keep units running at peak
efficiency.
Storing the UPS and Batteries
0T
If you store the UPS for a long period, recharge the battery every 6 months by
connecting the UPS to utility power. The internal batteries charge to 80% capacity in
less than 5 hours. However, we recommends that the batteries charge for 48 hours
after long-term storage. If optional EBPs are installed, see the recharge times listed
in Table 21 on page
48
. Check the battery recharge date on the shipping carton label.
If the date is expired and the batteries were never recharged, do not use the UPS.
Contact your service representative.
0T
Replacing Batteries
NOTE
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
0T
。
0T
The EBP can be replaced when UPS is ON, but be aware that if the utility fails at that
time , the load of the UPS may NOT be protected.
0T
If you prefer to remove input power to change the batteries, see “UPS Turn on and
Turn off” on page
33
.