47
Table 18. Electrical Output Connections (
0T
All
0T
Models)
Model
Output Connections
Output Cables
1K-
0T
RT
(IEC C13-10A)*6
IEC320 C14-10A
1.5K-
0T
RT
(IEC C13-10A)*6
IEC320 C14-10A
2K-
0T
RT
(IEC C13-10A)*6
(IEC C19-16A)*1
IEC320 C14-10A
IEC320 C20-10A
3K-
0T
RT
(IEC C13-10A)*6
(IEC C19-16A)*1
IEC320 C14-10A
IEC320 C20-10A
Table 19. Environmental and Safety (All Models)
208/230/240 Vac Models
Surge
Suppression
EN 61000-2-2
EN 61000-4-2, Level 4
EN 61000-4-3, Level 3
EN 61000-4-4, Level 4 (also on signal ports)
EN 6100-4-5, Level 4 Criteria A
EMC
Certifications
CE per IEC/EN 62040-2,
Class B
Class B
EMC
(Emissions)
IEC 62040-2:ed2:2005 / EN 62040-2:2006
Safety
Conformance
IEC 62040-1-1, IEC 60950-1
Agency
Markings
CE
Operating
Temperature
0°C to 40°C (32°F to 104°F) in Online mode, with linear
derating for altitude
NOTE Thermal protection switches load to Bypass in case of
overheating.
Storage
Temperature
-20°C to 40°C (-4°F to 104°F) with batteries
-25°C to 55°C (-13°F to 131°F) without batteries
Transit
Temperature
-25°C to 55°C (-13°F to 131°F)