51
cabinet number after set work mode to parallel mode. The
value can be 2~6, default value is 2.
Cabinet Paral Redunt Units:
Parallel redundancy cabinet number, can modify the
redundancy cabinet number after set work mode to
parallel mode. The value can be 0~5, default value is 0.
Output Freq:
Output frequency, The value can be 50Hz or 60Hz.
Output Volt Level:
Output voltage level, The value can be 220V, 230V, 240V.
Output Ivn Volt Regu:
Inverter voltage regulated, The value can be -5%~0~+5%, step is
0.5%, default value: 0.
Battery Group:
Must modify the numer to actual configuration, The value can be 1~8,
default value is 1.
Battery number:
Must modify the numer to actual configuration, The value can be
30~50, default value is 32.
Содержание HIP3300E
Страница 14: ...13 Side View Rear View Full configuration...
Страница 15: ...14 Connect coppper bar Mains bypass common copper bar...
Страница 29: ...28 3 9 3 UPS installation The whole systems are showed below 4 Operation 4 1 Operation Modes...
Страница 40: ...39...
Страница 41: ...40 4 3 3 Alarm View the alarm and history of the UPS and open or close the buzer...
Страница 45: ...44 4 3 4 1 Basic Setting Click basic setting enter by input the correct password The user password is 111111...
Страница 49: ...48...
Страница 59: ...58 4 3 5 1 USB Wizard History Output download history and setting record by USB...
Страница 60: ...59 4 3 5 1 1 Alarm Log Output 4 3 5 1 2 Setting Log Output...