20
the following requirements are met:
− Routing mode: Routing the cables over the cable ladder or bracket in a single layer
(IEC60364-5-52 middle E).
− The ambient temperature is 30°C.
− The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
− 90°C copper flexible cable.
− The length of the AC power cables of a UPS is no longer than 30 m and DC power cables
no longer than 50 m.
3.6.2
Power cable connector requirements
Model
Connector
Connection
Mode
Bolt Type
Bolt Hole
Diameter
Torque
100k-160k
Mains input
connector
Crimped OT
terminals
M10
10.5mm
26N•m
Bypass input
connector
Crimped OT
terminals
M10
10.5mm
26N•m
Battery input
connector
Crimped OT
terminals
M10
10.5mm
26N•m
Output
connector
Crimped OT
terminals
M10
10.5mm
26N•m
Grounding
connector
Crimped OT
terminals
M10
10.5mm
26N•m
200k
Mains input
connector
Crimped OT
terminals
M10
10.5mm
26N•m
Bypass input
connector
Crimped OT
terminals
M10
10.5mm
26N•m
Battery input
connector
Crimped OT
terminals
M10
10.5mm
26N•m
Output
connector
Crimped OT
terminals
M10
10.5mm
26N•m
Grounding
connector
Crimped OT
terminals
M10
10.5mm
26N•m
250k
Mains input
connector
Crimped OT
terminals
M12
13.5mm
26N
•
m
Bypass input
connector
Crimped OT
terminals
M12
13.5mm
26N
•
m
Battery input
connector
Crimped OT
terminals
M12
13.5mm
26N
•
m
Output
connector
Crimped OT
terminals
M12
13.5mm
26N
•
m
Grounding
connector
Crimped OT
terminals
M12
13.5mm
26N
•
m
300k
Mains input
connector
Crimped OT
terminals
M12
13.5mm
26N
•
m
Bypass input
connector
Crimped OT
terminals
M12
13.5mm
26N
•
m
Battery input
connector
Crimped OT
terminals
M12
13.5mm
26N
•
m
Содержание HIP3300E
Страница 14: ...13 Side View Rear View Full configuration...
Страница 15: ...14 Connect coppper bar Mains bypass common copper bar...
Страница 29: ...28 3 9 3 UPS installation The whole systems are showed below 4 Operation 4 1 Operation Modes...
Страница 40: ...39...
Страница 41: ...40 4 3 3 Alarm View the alarm and history of the UPS and open or close the buzer...
Страница 45: ...44 4 3 4 1 Basic Setting Click basic setting enter by input the correct password The user password is 111111...
Страница 49: ...48...
Страница 59: ...58 4 3 5 1 USB Wizard History Output download history and setting record by USB...
Страница 60: ...59 4 3 5 1 1 Alarm Log Output 4 3 5 1 2 Setting Log Output...