Temp Sensor Select:
temperature sensor type select. Has tow types: NTC and RS485.
NTC for single and short distance. Rs485 for multiple and far
distance.
Inter Power Walk in:
this is enable the UPS to control the interval that each rack
transfers from battery mode to normal mode, which reduces the impact on the
generator or power grid. The value can be 0~200, default value is 10.
Inter sleep mode:
when load less than the software setting value, same parallel rack will
turn to standby mode and if the load more than the setting value
some rack will turn to inverter mode after setting the sleep mode
enable. Default value is disable.
Paral Operation ID:
Parallel operation ID, must modify the ID after set work mode to
parallel mode. The value can be 1~6, default value is 1.
Cabinet Paral Basic Units:
Parallel cabinet number, must modify the tatal parallel