7 Servicing/Maintenance
49 of 72
Ama-Drainer-Box
7 Servicing/Maintenance
7.1 Safety regulations
DANGER
Power supply not disconnected
Danger to life!
▷
Pull the mains plug or disconnect all electrical connections and secure against
unintentional start-up.
DANGER
Work on the lifting unit by unqualified personnel
Danger of death from electric shock!
▷
Have system components modified and dismantled by authorised personnel
only.
WARNING
Insufficient stability
Risk of crushing hands and feet!
▷
During assembly/dismantling, secure the pump (set)/pump parts to prevent
tilting or tipping over.
7.2 Servicing/inspection
DANGER
Vent opening clogged
Gas accumulation!
Explosion hazard!
▷
Regularly check the vent line. The opening must never be clogged.
NOTE
A regular maintenance schedule will help avoid expensive repairs and contribute to
trouble-free, reliable operation with a minimum of maintenance expenditure and
work.
NOTE
For all inspection and servicing work to be carried out at regular intervals we
recommend taking out the maintenance contract offered by KSB.
Operational reliability will be improved by regularly checking the lifting unit's proper
functioning.
Check the inside of the waste water lifting unit for any deposits, especially in the
area of the float switch. Clean it if required.
KSB recommends regular maintenance in accordance with the following plan:
▪
Every
1
/
4
of a year for lifting units installed in industrial businesses
▪
Every
1
/
2
year for lifting units in multiple dwelling buildings
▪
Every year for lifting units installed in single-family houses