Fig. 26:
Fitting the float switch
732
81-39
81-45
L
Fig. 27:
Clearance L = 180 mm
Table 8:
Switching points
Size
Ama-Drainer
Switching point approx. [mm]
ON
OFF
4.. SE, SD / 10
230
120
4.. SE, SD / 35
280
190
5.. SE, SD / 10K
230
120
522 SD/11
310
110
5.5.1.3 Single-pump units – Installing the pump set
NOTE
In order to ensure tight sealing of the cable entry, carefully open the nubs of the
cable grommets using an awl. Do not use a knife to open them.