background image

9

Installation and commissioning

• 

Take off the intake hose from the burner 

connection and put it into the foreseen con-

nection at the lower side of the burner hood.

• 

Turn the switch at the control panel to "Pre-

heat" and activate the main switch.

• 

Mount all side panels of the BKM120.

The 3 kW electric heater now heats the complete 

fresh air intake pipe and the heat exchanger, 

the burner and the burner motor and the interior 

room with the boiler control.

After about 30 – 45 min (depending on the out-

door temperature), continue as follows:

• 

Take off the intake hose from the burner 

hood and put it onto the burner connection.

• 

Promptly, adjust the switch to "Boiler".

Then activate the boiler main switch. The switch 

will glow green. Depending on the operation 

mode, do the necessary adjustments as shown 

in the chapter "Control settings".

4.3.3  Secondary side

Until the operation temperature is reached, the 

boiler circulates the liquid internally. Only after 

that, the primary circuit is supplied and the 

energy can be taken off by the secondary circuit 

at the plate heat exchanger. The highest possible 

temperature raise depends from the flow rate. 

The following table indicates the calculated tem-

perature rise at different flow rates at the maxi

-

mum power of 120 kW. It only depends slightly 

from the entering temperature.

Flow rate [l/min]

Temperature rise [K]

50

35

100

17

150

12

200

8,6

At low entering temperatures (return temperatu-

res) of about <20 °C, the flow rate must not be 

higher than 75 l/min (4,5 m³/h, calculated flow 

rate). In addition to that, the boiler temperature 

must be set to 85 °C (see "Control settings"). 

Otherwise, undesired operation faults of the con-

trol may occur (pulsing control, long controlling 

time).

•  the secondary circuit is filled and deaerated.
• 

the cap valve B5 at the expansion vessel is 

opened.

• 

the condensate pipe and the neutralisation 

box are filled with water and free of ice.

• 

the valves B1, B2 and B3 are opened.

• 

all connections and screwings are sealed.

• 

the inlet air hose is put onto the burner.

At temperatures near or below the freezing point, 

you have to check if the siphon of the conden-

sate pipe and the neutralization box are ice-free. 

If they are not, you have to thaw the ice before 

commissioning using the heating band. Switch it 

on using the switch "Heat Neutrabox" at the con-

trol panel. When all the ice has melted, you can 

continue the commissioning work.

4.3.1  Commissioning at outdoor tempe-

ratures  >5 °C

At outdoor temperatures over 5 °C, pre-heating 

the burner and the inlet air components is not 

necessary. The changeover switch at the control 

panel must be adjusted do "Boiler". Then acti-

vate the boiler main switch. The switch will glow 

green. Depending on the operation mode, do the 

necessary adjustments as shown in the chapter 

"Control settings".

4.3.2  Commissioning at outdoor tempe-

ratures  <5 °C

In case of too low outdoor temperatures, the fol-

lowing problems may occur:
1.  Condensate leftovers from last operation 

can be frozen and thus hinder the newly 

created condensate to flow away.

2.  If a not suitable fuel is used or if a not sui-

table fuel is still inside the oil pipe, paraffin 

may have been created blocking now the oil 

pipe.

3.  If the intake air is too cold, it may happen 

that there is no flame at the burner.

4.  The bearing grease inside the burner motor 

can be too viscous so that the motor does 

not start.

For point 1, set the switch „Heat Neutrabox“ to 

„1“. For point 2 observe the table on chapter 

"Mounting and connecting". For points 3 and 

4, you have to do the pre-heating programme 

before the actual commissioning. This is how to 

do it:

Содержание BKM120

Страница 1: ...Operation Manual BKM120 Mobile hot water unit 053373 00c July 2014 0085 ...

Страница 2: ......

Страница 3: ...ical connection 8 4 3 Commissioning 8 4 3 1 Commissioning at outdoor temperatures 5 C 9 4 3 2 Commissioning at outdoor temperatures 5 C 9 4 3 3 Secondary side 9 5 Decommissioning 10 5 1 Boiler shutdown 10 5 2 Disassembling the unit 10 6 Control settings 11 6 1 Normal heating mode 11 6 2 Manual heating mode 11 6 3 Standby mode 11 6 4 Boiler temperature 11 7 Maintenance and servicing 12 7 1 Cleaning...

Страница 4: ...on of the heating circuit is a plate heat exchanger In the following the circuit of the heat transfer medium between boiler and heat transformer will be called primary circuit or primary side The circuit which is connected externally and flowing through the heat transformer at the opposite side will be called secondary circuit or secondary side Note The burner is supplied with oil oil connection a...

Страница 5: ...ck B3 Absperrhahn Shut off cock B4 Kesselfüll und entleerhahn Filling and discharging cock B5 Kappenventil Cap valve B6 Hahn für Belüftung Valve for aeration B7 Entleerhahn Sekundärseite Discharging cock secondary V1 Entlüfter Primärseite Vent valve primary side V2 Entlüfter Sekundärseite Vent valve secondary side V3 Entlüfter Wärmeübertrager Vent valve heat exchanger V4 Sperrventil Blocking valve...

Страница 6: ...h Max pressure primary circuit 300 kPa Max pressure secondary circuit 800 kPa Pressure drop secondary side 16 kPa Max outlet temperature 80 C Connections Secondary flow and return 2 BSP internal thread Oil pipe Quick coupling female Filling discharging primary circuit 1 2 hose connection Discharge heat exchanger 1 2 internal thread Electric connection Voltage 230 V Amperage 16 A Plug blue IEC60309...

Страница 7: ...5 General 1 5 Circuit diagram ...

Страница 8: ...KM120 must only be operated when it is in a technically proper condition Faults or damages that could or do alloy the safety must be repaired immediately and professionally Damaged elements and unit components must only be replaced by original Kroll spare parts Always observe the regulations warnings of the local safety regulations during loading transport to or from site as well as during storage...

Страница 9: ...front side rear side onto rear side Warning When the units are stacked never do any maintenance cleaning or other work neither at the upper unit nor at the lower unit Warning 3 Transport and storage 3 1 Transport Before transport make sure that all connections have been removed This means the electrical connections the oil feeding line and the secondary connection water connection the chimney has ...

Страница 10: ...ry circuit there is a pressure of minimum 1 5bar if the pressure is lower you have to add heat transfer liquid see chapter Maintenance and servicing 4 Installation and commissio ning Fig 1 Control panel BKM120 Main switch BKM120 Light Main switch boiler Boiler control Changeover switch Preheat Boileroperation Heating of neutralization box and siphon Signal lamp bur ner malfunction Resetbutton for ...

Страница 11: ...ng controlling time the secondary circuit is filled and deaerated the cap valve B5 at the expansion vessel is opened the condensate pipe and the neutralisation box are filled with water and free of ice the valves B1 B2 and B3 are opened all connections and screwings are sealed the inlet air hose is put onto the burner At temperatures near or below the freezing point you have to check if the siphon...

Страница 12: ...eating oil from the oil pipes and the oil filter and deaerated device To shutdown the boiler proceed as follows Push the ESC button several times until the ESC text expires Use the rotary knob to set Select function and confirm Select Boiler and confirm Push the left central quick select button twice Set the operation mode to Off and confirm with Save Wait for at least 5min only then switch the bo...

Страница 13: ...rol may occur pulsing control long controlling time Setting Push the ESC button several times until the ESC text expires Use the rotary knob to set Settings MB and confirm Select Enter password and confirm Enter the password 234 and confirm 6 Control settings Generally consider the operating manual of the master control Note Mostly settings are only done at the secondary side These settings are in...

Страница 14: ...e the siphon and wash it out with water Then wash the synthetic heat exchanger from the front see burner manual chapter 7 4 Wet cleaning neutralization box and plastic heat exchanger The water leaves at the back via the drain channel of the BKM120 In order to clean the granulate fill it into a sepa rate basin first There wash it with clear water decant the water and refill the cleaned granulate ba...

Страница 15: ... which can be discharged via the primary drain bolt For ventilation open the ball valve B6 Ideally the discharged heat trans fer liquid should be collected The heat trasferring liquid Glykosol N is classi fied with water hazard class 1 as slightly water endangering Note Now you can unscrew the four bolts two at the primary side and two at the secondary side and loosen the cover plate of the heat e...

Страница 16: ...BKM120 14 EC conformity certification 8 EC conformity certification EG Konformitätserklärung Déclaration de conformité CE ...

Страница 17: ...15 Notes 9 Notes Notes and particularities ...

Страница 18: ...BKM120 16 Notes Notes and particularities ...

Страница 19: ...17 Notes Notes and particularities ...

Страница 20: ...ment design shall result in expiration of every guarantee claim Otherwise our Conditions of Sale and Delivery shall apply Subject to technical change in terms of product improvement without notice updated 2016 01 29 08 16 Kroll GmbH company Pfarrgartenstraße 46 D 71737 Kirchberg Murr Phone 0049 0 7144 830 200 Fax 0049 0 7144 830 201 E mail mail krolluk com Internet www kroll de ...

Отзывы: