TECHNICAL DATA
72
H250
www.krohne.com
04/2009 - 4000269302 MA H250-R02
Indicator M9 ESK3-PA Profibus
Terminal connection
2.5 mm
2
Bus cable R
´
15...150 Ohm/km
Bus cable L
´
0.4...1 mH/km
Bus cable C
´
80...200 nF/km
M9 ESK3PA Hardware
Hardware
acc. to IEC 1158-2 and FISCO model
Supply voltage
9...32 VDC
Base current
12 mA
Starting current
< base current
FDE (fault drop electronics)
< 18 mA
Accuracy acc. to VDI/ VDE 3513
1.6
Measurement resolution
< 0.1% full scale value
Temperature influence
< 0.05% / K full scale value
Software firmware version
1.01/000418
Ident No.
3184980200
M9 ESK3PA Software
GSD
Devices master file
Device profile
Profiles B, V3.0
Function blocks
Flow rate (AI0)
Volume or mass
Totalizer (TOT0)
Volume totalizer
Default unit: [m
3
]
Totalizer (TOT1)
Mass totalizer
Default unit: [kg]
Address range
0...126, default 126
SAP`s
Service Access Points
DD
Device Description