background image

Remote Control 

The Proflame transmitter uses radio frequency to communicate information to the receiver box 
located in the fireplace.   
 
The transmitter is powered by three (3) AAA batteries.  As these batteries begin to wear down 
the blue backlight feature on the remote will deactivate indicating the batteries as beginning to 
lower.  Approximately after this happens the homeowner has about 2 - 3 weeks to change out 
batteries.  
 
There is also an indicator on the display to indicate low battery in transmitter.   

Blue back lit LCD display 

ON /OFF Key 

Thermostat Key 

UP / DOWN Arrow Key 

Mode Key 

CPI Mode  

Содержание SIT Proflame II

Страница 1: ...ation will assist you through this process Kozy Heat welcomes your questions while you are at the job site 800 253 4904 This guide is ONLY intended for professional or trained technicians June 2012 R1...

Страница 2: ...2 System Overview The primary components that are included in the SIT Proflame II GTMFS System Gas Valve Integrated Fireplace Control IFC SIT Pilot Assembly Transmitter remote control GTMF model...

Страница 3: ...o 1 0VDC test image shown on pg 16 Gas Pressure Very Important for the Function of an IPI Pilot Assembly Inlet Pressure Test Point Measures amount of gas coming into the valve NG 5 0 WC to 7 0 WC LP 1...

Страница 4: ...ower loss Testing Power Voltage AC Power Pins red and black would be about 6 5VAC See test images on pg 15 Diagnostic LEDs This area contains LEDs which provides the technician with lockout codes For...

Страница 5: ...me into two for burner and flame sensor Igniter provides spark to the pilot hood Flame Sensor Rectifies the pilot is lit and carries the voltage to the IFC module to stop spark ing and allow main burn...

Страница 6: ...e batteries begin to wear down the blue backlight feature on the remote will deactivate indicating the batteries as beginning to lower Approximately after this happens the homeowner has about 2 3 week...

Страница 7: ...th ability to manually set the flame height OFF Thermostat is off but will operate manually from remote using ON OFF key SMART Works just the same as ON thermostat but the SMART function will modulate...

Страница 8: ...hermostat Key and the Mode Key at the same time Continuous Pilot Intermittent Pilot CPI IPI This system has the option of a continuous standing pilot feature By having the pilot on continuously the fi...

Страница 9: ...approximately 2 seconds press it again Reset Using the Remote Flame Adjustment buttons In the manual mode use the down arrow to lower the flame all the way to OFF Wait 2 seconds and then use the up a...

Страница 10: ...n a lockout position See page 9 on lockout and reset information Press the Red SW1 button the on the IFC module You should hear 3 fast beeps indicating the receiver box is ready to learn the remote co...

Страница 11: ...oper grounding 6 Check continuity of valve coil Image on pg 16 If no continuity replace valve 8 Verify proper voltage at pilot valve connection Image on pg 15 If voltage is present and no gas released...

Страница 12: ...gas valve valve not opening Main burner ignites No 1 Verify the receiver switch is in ON position If in the REMOTE position verify remote is powered ON and thermostat is OFF 2 Verify electrical connec...

Страница 13: ...rify the ON OFF rocker switch is in the ON position 3 Verify there is power at the outlet the fan plugs into 4 Verify the remote does not say OFF on remote Note Fan in thermo settings is time delay 5...

Страница 14: ...etting 0VAC out of this test make sure the POWER switch is in the ON position and if so test the outlet the unit is plugged into for power Note This test will be a VAC reading Figure 1 3 would be the...

Страница 15: ...4 292VDC Figure 2 1 and drop to about 0 940 Figure 2 2 This reading tells us the IFC module is sending power through the harness to open the corresponding solenoid If you are getting power and valve i...

Страница 16: ...ition and disconnect the wiring harness from EV1 and EV2 Using one multimeter pin on the solenoid and the other on the ground your reading should be approximately 331 4 ohms Same process is conducted...

Страница 17: ...timeter would need to be in the Ohms position and disconnect wiring harness from the step motor to expose the leads Using a multimeter place the two pins on the two leads of the connector Your reading...

Страница 18: ...would need to be in the DC voltage position Using one multimeter pin on the black lead and the other on the white lead your reading should be approximately 118 VDC on HI Same process is conducted for...

Страница 19: ...19 Battery Pack 885 Proflame Flame Sensor Main ON OFF Switch Pilot Burner Igniter Pilot SW1 Button red IFC Control Module Appliance Ground Star Main Line Variable Speed Fan Variable Lights...