10 

Remote Not Learning to Receiver 

Begin 

Verify proper 120VAC power supply 
 

A.  Remove the batteries from battery back up. 

 

B.  Attempt to light continuous pilot from switch.  If pilot lights or if spark is present we know power is 

supplied and we can proceed.  If spark or pilot is not present proceed in troubleshooting steps for pilot does not 
light.  (if you now re-install batteries and the pilot turns on focus would be on main power supply which is ex-
plained later in the guide with voltage readings) 

It is possible the integrated fireplace control (IDC) module is in a lockout position. See page 9 on lockout and reset 
information.  

Press the Red  SW1 button the on the IFC module.  You should 
hear 3 fast beeps indicating the receiver box is ready to learn the 
remote code.  Did you hear the beep code? 

Verify the ON/OFF rocker switch is 
in the ON position. Attempt learn 
sequence again. If no sound/LED 
replace IFC module.  

No  

Yes  

Quickly press the ON/OFF power button on the remote control.  
You should now hear 4 beeps indicating the receiver has learned 
the remotes unique programming code. Did you hear the beep? 

Verify batteries are new in remote, 
and if so replace remote control.  

No  

Yes  

Remote is learned to the receiver and should operate the fireplace.   

Proceed to next troubleshooting 
tree to verify there is not another 
problem  

No  

Содержание SIT Proflame II

Страница 1: ...ation will assist you through this process Kozy Heat welcomes your questions while you are at the job site 800 253 4904 This guide is ONLY intended for professional or trained technicians June 2012 R1...

Страница 2: ...2 System Overview The primary components that are included in the SIT Proflame II GTMFS System Gas Valve Integrated Fireplace Control IFC SIT Pilot Assembly Transmitter remote control GTMF model...

Страница 3: ...o 1 0VDC test image shown on pg 16 Gas Pressure Very Important for the Function of an IPI Pilot Assembly Inlet Pressure Test Point Measures amount of gas coming into the valve NG 5 0 WC to 7 0 WC LP 1...

Страница 4: ...ower loss Testing Power Voltage AC Power Pins red and black would be about 6 5VAC See test images on pg 15 Diagnostic LEDs This area contains LEDs which provides the technician with lockout codes For...

Страница 5: ...me into two for burner and flame sensor Igniter provides spark to the pilot hood Flame Sensor Rectifies the pilot is lit and carries the voltage to the IFC module to stop spark ing and allow main burn...

Страница 6: ...e batteries begin to wear down the blue backlight feature on the remote will deactivate indicating the batteries as beginning to lower Approximately after this happens the homeowner has about 2 3 week...

Страница 7: ...th ability to manually set the flame height OFF Thermostat is off but will operate manually from remote using ON OFF key SMART Works just the same as ON thermostat but the SMART function will modulate...

Страница 8: ...hermostat Key and the Mode Key at the same time Continuous Pilot Intermittent Pilot CPI IPI This system has the option of a continuous standing pilot feature By having the pilot on continuously the fi...

Страница 9: ...approximately 2 seconds press it again Reset Using the Remote Flame Adjustment buttons In the manual mode use the down arrow to lower the flame all the way to OFF Wait 2 seconds and then use the up a...

Страница 10: ...n a lockout position See page 9 on lockout and reset information Press the Red SW1 button the on the IFC module You should hear 3 fast beeps indicating the receiver box is ready to learn the remote co...

Страница 11: ...oper grounding 6 Check continuity of valve coil Image on pg 16 If no continuity replace valve 8 Verify proper voltage at pilot valve connection Image on pg 15 If voltage is present and no gas released...

Страница 12: ...gas valve valve not opening Main burner ignites No 1 Verify the receiver switch is in ON position If in the REMOTE position verify remote is powered ON and thermostat is OFF 2 Verify electrical connec...

Страница 13: ...rify the ON OFF rocker switch is in the ON position 3 Verify there is power at the outlet the fan plugs into 4 Verify the remote does not say OFF on remote Note Fan in thermo settings is time delay 5...

Страница 14: ...etting 0VAC out of this test make sure the POWER switch is in the ON position and if so test the outlet the unit is plugged into for power Note This test will be a VAC reading Figure 1 3 would be the...

Страница 15: ...4 292VDC Figure 2 1 and drop to about 0 940 Figure 2 2 This reading tells us the IFC module is sending power through the harness to open the corresponding solenoid If you are getting power and valve i...

Страница 16: ...ition and disconnect the wiring harness from EV1 and EV2 Using one multimeter pin on the solenoid and the other on the ground your reading should be approximately 331 4 ohms Same process is conducted...

Страница 17: ...timeter would need to be in the Ohms position and disconnect wiring harness from the step motor to expose the leads Using a multimeter place the two pins on the two leads of the connector Your reading...

Страница 18: ...would need to be in the DC voltage position Using one multimeter pin on the black lead and the other on the white lead your reading should be approximately 118 VDC on HI Same process is conducted for...

Страница 19: ...19 Battery Pack 885 Proflame Flame Sensor Main ON OFF Switch Pilot Burner Igniter Pilot SW1 Button red IFC Control Module Appliance Ground Star Main Line Variable Speed Fan Variable Lights...

Отзывы: