SIT Proflame 2 IFC Module Ignition and Reset Information
Ignition Sequence:
Starting from OFF, press the remote power button. Approximately four seconds after it is pushed the IFC module
will send spark to the pilot hood. It will spark for 60 seconds.
If there is no flame ignition (rectification) during the first try for ignition, the IFC module will stop sparking for
approximately 35 seconds and then it will begin sparking again. The second attempt will spark for another 60 se-
conds.
If there is no positive rectification after the second sequence the IFC module will go into a Lock Out and the LED
Indicator Light will blink three times in intervals until the system is reset.
In Summary:
1) Ignition sequence is 60 seconds spark, 35 second wait, 60 second spark and then lock
out if flame is not rectified.
2) Lock Out blink on the LED Indicator Light is 3 blinks in sequence
Resetting Proflame IFC Module When In Lock Out:
Reset Using the Transmitter ON/OFF power button:
Turn the system off by pressing the remote power button. After approximately 2 seconds press it again.
Reset Using the Remote Flame Adjustment buttons:
In the manual mode, use the down arrow to lower the flame all the way to OFF. Wait 2 seconds and then
use the up arrow to turn the flame back on.
Reset Using Receiver Switch:
With the remote off, move the ON-REMOTE-OFF switch to the OFF position on the receiver box. Wait
approximately 2 seconds and slide back to ON position. (Note: You will need to move to REMOTE if
you prefer to turn on via remote).
Low Battery Condition (<4V) Remote Control:
Battery Icon will appear on LCD remote control display. Replace batteries.
Low Battery Condition (<4V) Battery Backup:
Red
LED Indicator will blink (1) time in intervals. Low double-beep emit-
ted from IFC control module when it receives an ON/OFF command from the remote control. Replace Batteries.
Pilot Flame Error Condition:
Red
LED Indicator will blink (2) times in intervals. Contact your dealer if this occurs.
System Lock Out Condition:
Red
LED Indicator will blink (3) times in intervals. Make sure gas is turned on. Make sure sen-
sor is not shorted. Follow
Reset IFC Control Module When System Goes Into Lock Out
instructions above.