16
COMPLETE THE CONVERSION:
1.
Adjust front burner venturi setting by loosening screw, adjusting cap and
retightening screw.
NAT: 100% closed / LP: 100% open
2.
Re-install burner assemblies into fireplace, checking to ensure burner venturis
are properly seated over burner orifices.
3. Back (main) burner venturi adjustment handle is attached to underside of
control board. Access through lower grill opening. Loosen wing nuts, adjust
as necessary, pulling handle forward to open, pushing backwards to close.
Tighten wing nuts.
NAT: 1/8” (3mm) open - handle pushed back
LP: 5/8” (16mm) open - handle pulled forward
Venturi may need further adjustment, depending on venting configuration.
4.
Adjust combustion air intake shield*.
5.
IF CONVERTING TO LP GAS:
Remove baffle shield.
IF CONVERTING TO NAT GAS:
Install baffle shield included with kit
6.
Re-install pilot shield.
7.
Reinstall any light kit components if previously removed.
8.
Re-install ember refractory and logs*.
9.
Turn on gas and electrical supplies.
10. Light fireplace*. Check for leaks at all connections with soapy water, whether
field or factory made.
11. Test inlet pressure, referring to page 13 for proper testing procedures. Chart
below states proper pressure readings. Visually check pilot flame. Flame
should envelope top of flame sensor and extend onto burner far enough for
proper ignition. To Adjust Pilot: Turn pilot adjustment screw clockwise to
decrease or counter-clockwise to increase pilot flame.
12. Turn fireplace off.
13. Affix gas type sticker to existing label.
14. Reinstall glass frame assembly, upper louver and upper hood*.
15. Verify proper ignition and operation of fireplace. Refer to page 17 for proper
pilot and burner flame appearance and adjustment.
16. Complete and affix ‘Gas Conversion” label behind lower grill.
*REFER TO FIREPLACE INSTALLATION MANUAL IF NECESSARY.
CONVERSION KIT INSTRUCTIONS
Baffle shield location
Figure 16b
GAS CONVERSION LABEL
(included with conversion kit)
Figure 16c
CONVERT THE GAS CONTROL VALVE:
Follow stepper motor pressure regulator instruction sheet included with conversion
kit to convert gas valve. (LP or NAT marked on stepper motor pressure
regulator).
PROPER BURNER / PILOT ASSEMBLY ORIENTATION
(shown without pilot shield for clarity purposes)
Figure 16a
NATURAL GAS
LP GAS
MINIMUM INLET GAS PRESSURE
5” WC (1.25 kPa) (7” WC (1.74 kPa) recommended)
12” WC (2.99 kPa) (recommended)
MAXIMUM INLET GAS PRESSURE
10.5” WC (2.62 kPa)
13” WC (3.24 kPa)
MANIFOLD PRESSURE (HI)
3.8” WC (.95 kPa)
11” WC (2.74 kPa)
MANIFOLD PRESSURE (LO)
1.1” WC (.27 kPa)
2.9” WC (.72 kPa)