Page 5
9. The heater must be turned off and allowed to cool before cleaning.
Make sure there are no hot ashes or embers in the burn pot, ash tray or
combustion chamber. Use a brush and scoop to clean. DO NOT USE
A VACUUM CLEANER.
10. This heater is POWER VENTED. The vent pipes have positive
pressure during operation. It is IMPERATIVE that all joints in the
venting system be sealed to prevent any leakage of exhaust gases
inside the house. All joints must be sealed using high temperature
silicone sealer (RTV).
11. Store pellet fuel at a safe distance (at least 36 inches/1 meter) away
from the heater.
12. Use of outside combustion air is MANDATORY (unless an APR Part
No CV100 check valve is used). Connect the air intake of the heater to
the exterior of the building with a non-combustible metal pipe with a
minimum diameter of 2 inches (50 mm). Use of plastic pipe is not
permitted.
13. Follow this manual carefully for proper installation. If you are
uncertain, call your dealer. Most of the dealers have qualified and
trained installers. We highly recommend the use of their services.
2. Clearance to Combustible Walls
2.1 Free Standing Stove
A. Side wall to Unit
5 inches
125 mm
B. Back wall to Unit
1 inch
25 mm
C. Corner to Unit
1 inch
25 mm
2.2 Free Standing Stove Installed in Alcove.
Alcove dimensions must be:
A. Minimum width
34 inches
865 mm
B. Minimum height
48 inches
1220 mm
C. Maximum depth
30 inches
760 mm
2.3 Insert Installed in Masonry or Listed Factory Built Fireplace.
Minimum clearance must be:
A. Side wall to Unit
5 inches
125 mm
B. Mantle to Unit
13 inches
330 mm
C. Top facing to Unit
13 inches
330 mm
D. Side facing to Unit
5 inches
125 mm
E. Floor Protector
6 inches
150 mm