Tank emptying
In order to empty the tank:
•
turn off the valves which connect the buffer tank with central heating system,
•
turn off the valves which connect the buffer tank with PC circuit,
•
turn off the valve to connect the cold water inlet with cylinder,
•
turn off the valve on the cold water inlet,
•
turn on the drain valve.
EN
Start up
Before the start-up make sure that the installation procedures have been carried out in
accordance with the regulations included in this manual.
Cylinder must be filled with water:
-
turn on the valve on cold water supply pipe,
-
turn on the hot water outlet valve (water outflow without the air bubbles indicates
that the tank is full),
-
turn off the outlet valves.
Turn on the valves connecting cylinder with the central heating system and fill the
surface area of buffer. To vent the buffer, you should use air vent on supply. Air vent is
also recommended at the highest point of the coil supply connection. Check for water
and heating medium leaks. Check out the safety valve performance in accordance with
valve manufacturer’s instruction.