1.3.4. Cooler and Heater Sections
Cooler section is fitted with water or direct evaporation (DX) coolers as well as combined heater/cooler heat exchangers.
Cooling air causes condensation, therefore, a condensate tray is installed under a heat exchanger. If air velocity in the air
handling unit is high (> 2 m/s), an optional drop eliminator is installed, which prevents condensate from entering other parts
of the unit or air ducts.
1
2
3
4
2
3
1
Fig. 8.
Cooler section
1 – drop eliminator, 2 – coil for water/refrigerant 3 – condensate tray,
4 – cooler section label
Depending on the order, electric or water heaters may be selected. An electric heater section is fitted with heater control
electronics and the main circuit breaker (see Chapter “Requirements for Electrical Connection”). A water heater is fitted with
a return water temperature sensor, which protects the heat exchanger against freezing. Sensor installation procedure is
described in Chapter “Installation of External Heating/Cooling Devices”.