• Numbers indicate
the order of activation. All units have an integrated electrical heater, therefore it is factory-assigned
as Stage 1. You can also assign an “external coil” (duct-mounted water heater/cooler) or an “external DX device” (direct
evaporation unit) as a stage. If an external coil is selected, you also must specify its type: “Hot water” (used for heating),
“Cold water” (used for cooling). If additional heating/cooling devices are not available, you do not want to use them or an
electric heater, select “None”.
If you turn an electric heater off and do not use a duct-mounted heater, the desired air temperature
may not be reached when the outside air is cold.
• Allow dehumidification with cooling
– this setting must be enabled to use a DX unit or duct-mounted water cooler to
dehumidify the supply air. An option to enter a value for desired humidity will appear in the settings of standard ventila-
tion modes (see Chapter 2.6.2).
AIR QUALITY
– here you can activate and set-up air quality control which will be used in AUTO mode (see Chapter 2.6.2):
• Impurity control
– turning on/off an impurity control function. At least one CO2 or VOC sensor must be connected to the
controller board to activate this function (see Chapter 2.6.2.). If ventilation by a weekly schedule is required, this function
must be turned off.
• Humidity control
– turning on/off a humidity control function. Humidity control function requires a humidity sensor. If
no humidity sensor is connected to the controller board, sensor integrated in a control panel will be used for this purpose
(see Chapter 2.6.2.).
• Sensor 1
– specify the type of the sensor connected to a terminal B8 (see “Installation Manual”). If this sensor is not
available, select “None”.
• Sensor 2
– specify the type of the sensor connected to a terminal B9 (see “Installation Manual”). If this sensor is not
available, select “None”.
• Outside humidity
– this option appears only if one of the sensors is of RH type (humidity sensor). If any of the connected
sensors are installed in the outdoor air flow, specify which one. If none of the installed humidity sensors measure the
outside humidity, select “None”.
• Minimum intensity
– select ventilation intensity at which the unit will operate when air quality (impurity or humidity) is
good. If 0% is selected, the unit will stop when air impurity level is low.
• Maximum intensity
– select ventilation intensity limit, under which the unit will operate when air quality (impurity or
humidity) exceeds a defined value.
• Check period
– specify how often the unit shall turn on to check air quality, when minimum intensity is set to 0%.
FILTERS
– once filters are replaced, calibrate new filters and confirm replacement in the unit.