Flow control
– select a method for air flow control (see Chapter 2.1). Selected CAV or DCV air flow control allows additional
corrections of supply and extract air measurements, when the measured air volume does not match the actual one. This may
also be due to design features of the duct system, for example, wrong diameter ducts, excessive number branches or elbows,
or installation without following the installation recommendations. When a VAV mode is selected, a measurement range
of pressure sensors connected to the main board must be additionally entered (see “Installation Manual”), i.e. maximum
pressure Pa that the sensor is measuring by 10V output (measurement range is specified in the VAV sensor manual).
Flow control mode
CAV
Supply flow correction
0 m3/h
Extract flow correction
0 m3/h
Flow control
Flow control
Flow control mode
CAV
VAV
DCV
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
• Impurity control
– turning on/off an impurity control function. At least one CO2 or VOC sensor must be connected to the
controller board to activate this function (see Chapter 2.6.2.). If ventilation by a weekly schedule is required, this function
must be turned off.
• Humidity control
– turning on/off a humidity control function. Humidity control function requires a humidity sensor. If
no humidity sensor is connected to the controller board, sensor integrated in a control panel will be used for this purpose
(see Chapter 2.6.2.).
• Sensor 1
– specify the type of the sensor connected to a terminal B8 (see “Installation Manual”). If this sensor is not
available, select “None”.
• Sensor 2
– specify the type of the sensor connected to a terminal B9 (see “Installation Manual”). If this sensor is not
available, select “None”.
• Outdoor humidity
– this option appears when one of the sensors is of RH type (humidity sensor). If any of the connected
sensors are installed in the outdoor air flow, specify which one. If none of the installed humidity sensors measure the
outside humidity, select “None”.
Air quality control
1
/ 2
Impurity control
On
Humidity control
On
Sensor 1
CO2
Sensor 2
RH
Outdoor humidity
None
Sensor 1
None
CO2
VOC
RH
Air quality control
1
/ 2
Impurity control
On
Humidity control
On
Sensor 1
CO2
Sensor 2
RH
Outdoor humidity
None
Outdoor humidity
None
Sensor 1
Sensor 2
Air quality control
– here you can activate and set-up
air quality control which will be used in AUTO mode (see
Chapter 2.6.2).
Air quality control
1
/ 2
Impurity control
On
Humidity control
On
Sensor 1
CO2
Sensor 2
RH
Outdoor humidity
None
2
/ 2
Air quality control
Minimum intensivity
0 %
Maximum intensivity
70 %
Check period
2h