3.4.4. ECO and AUTO mode settings
You can change the settings of these modes by pressing the “Modify” button below the ECO and AUTO buttons. More
information on these function see in Chapters 2.5 and 2.6. After changing the settings, press “Save changes” button at the
bottom of the window. Press the return symbol at the top to return to the main window.
CONTROL
OPERATION CONTROL
Min. supply air temperature
Max. supply air temperature
Free cooling
Heater blocking
Cooler blocking
15.0 °C
25.0 °C
SAVE CHANGES
RESTORE TO DEFAULT
ECO
AUTO
Air temperature
Air Impurity
Air humidity
Electric heater
20.0 °C
800 ppm
60 %
3.4.5. Ventilation by a weekly schedule
To activate ventilation by a weekly schedule, press AUTO
1
and select a desired operation schedule in the SCHEDULING
section. Button of the selected schedule will change its colour.
SCHEDULING
OPERATION PROGRAM
MODIFY >
SCHEDULE
I
II
III
IV
V
VI
VII
4:00
8:00
12:00
16:00
20:00
24:00
WORKING WEEK
STAY AT HOME
CUSTOM
OFFICE
1
Ventilation by a weekly schedule is not possible when air quality control function is activated.