1.4. Temperature sensor installation
The temperature sensor B1 (Fig. 1.4 a) of the delivered airflow must be installed in the air duct of delivered air
to the premises past all the additional air heating/cooling equipment (if any). It is recommended to install the
sensor in the straight segment of the air duct with the distance of 5 diameters in front of the sensor and behind
of it (Fig. 1.4 c).
The flat part of sensor must be directed perpendicularly to the airflow for
sensing element would be well blown.
The water temperature sensor B5 (Fig. 1.4 b.) is mounted on the return water pipe, by screwing it into the pro
-
vided hole. The sensor must be thermally insulated!
Supply air temperature sensor B1
Water temperature sensor B5
Fig. 1.4 a
Fig. 1.4 b
B1
D
B
>5D
>5D
D/2
Fig. 1.4 c