TS_616_08 PW8000DPA ST (S2) User Manual 21/4/22
79
9: Specification
9.3
Battery Data
Heat Dissipation With Non-linear Load
10 kVA UPS module
20 kVA UPS module
Heat dissipation with 100% non-linear load. Per module
(EIN 62040-1-1:2003
W
550
1100
Heat dissipation with 100% non-linear load. Per module
(EIN 62040-1-1:2003)
BTU/h
1887
3754
Airflow (25° - 30°C) with non-linear load.
Per module (EIN 62040-1-1:2003)
m³/h
150
150
Dissipation at no load
W
120
150
Module efficiency
Efficiency ac-ac up to (at Cosφ 1.0)
(depending on % module power)
100%
75%
50%
25%
95.5%
95.5%
95.0%
94.5%
Efficiency with linear load at cosφ = 0.8ind
Efficiency non-linear load (EN 62040-1-1:2003)
Typically up to 1% higher of above values
Typically up to 1% lower of above values
ECO mode efficiency at 100% load
%
98%
Environmental Characteristics
Audible noise with 100% / 50% load
dBA
55 / 49*
57 / 49*
Operation temperature
°C
0 – 40
Ambient temperature for batteries (recommended)
°C
20
Storage temperature
°C
-25 - +70
Battery storage time at ambient temperature
Max. 6 months
Max. altitude (above sea level)
m
1000m (3300ft) without de-rating
De-rating factor for use at altitudes above 1000m sea
level according to (IEC 62040-3) (ALL MODULES)
Height above sea level (m / ft)
De-Rating Factor for Power
1500 / 4850
0.95
2000 / 6600
0.91
2500 / 8250
0.86
3000 / 9900
0.82
Relative air-humidity
Max. 95% (non-condensing)
Accessibility
Totally front accessibility for service and maintenance
* These are approximate figures for one module only.
The audible noise also depends on the characteristics of the host cabinet in which the UPS sub-rack is fitted.
Battery characteristics
10 kVA UPS module
20 kVA UPS module
Battery type
Maintenance free VRLA or NiCd
Permitted number of VRLA 12V battery blocks
No.
30-50 *
40-50
*
Permitted number of 1. NiCd cells
No.
300-500 *
400-500
*
Maximum battery charger current
A
4 A (6A on request)
Battery charging curve
Ripple free: IU (DIN 41773)
Temperature compensation
Standard (temp. sensor optional)
Battery test
Automatic and periodically (adjustable)
*
Depending of the effective load in kW used by the module