3: Installation Planning
3.3.3 Parallel cabinet cabling recommendations
In order to achieve equal load sharing between the various UPS cabinets in a multi-cabinet installation, the input cables
from the mains switchboard to each UPS cabinet should be of equal length. Similarly the UPS output cables to the output
(load) distribution panel should be of approximate equal length.
Figure 3.10 Parallel cabinet cabling considerations
Mains Switchboard
Output (Load) Distribution Panel
CORRECT
Mains Switchboard
Output (Load) Distribution Panel
INCORRECT