2: General Description
20
TS_616_08 PW8000DPA ST (S2) User Manual 21/4/22
Figure 2.15 UPS Interface Boards
2
3
4
6
8
9
10
11
12
5
7
1
2
3
4
6
8
9
10
11
12
5
7
1
X1
1
10
Customer Interface Board
1
SLOT 1 Slot for optional Modem/Ethernet card ONLY.
2
SLOT 2 Slot for optional SNMP card ONLY.
3
JR2
RJ45 Port: (Not used)
4
X2
Customer output dry ports (Phoenix terminal block):
Up to 5 output dry contacts used for signalling of the status of the UPS
system (e.g. mains failure, load on inverter, battery low, common alarm).
5
X1
Customer input dry ports (Phoenix terminal block):
Up to 5 input dry contacts used for remote shut down and generator
operation facilities, battery temp sensor or bespoke customer function.
6
LEDs
Status LEDs (red/green):
2 LEDs that indicate the customer interface board operational status.
The red led indicates a circuit board fault that most likely requires a board
replacement. The flashing rate of the green led indicates the board’s status
and normally flashes twice/second when the board is healthy.
7
JD1
RS232 Smart port computer interface:
A Sub D-9 female connector that provides an RS232 interface for remote
systems monitoring using a computer application, such as WAVEMON.
This allows the computer terminal to continuously monitor the mains
voltage and computer operating status, and process any alarm messages.
8
USB
Standard USB interface:
Provides a USB user interface for remote systems monitoring, as above.
Parallel Interface Board (fitted in a parallel UPS cabinet only)
9
X1
Sync Input:
Allows an external synchronisation control source to be connected.
10
X2
External manual bypass:
Auxiliary signals from external manual bypass switch and (optional)
external output breaker providing open/close status information for parallel
system configuration
11
S1-6
Configuration DIP switch:
Used to configure the cabinet position in a parallel system.
12
JD8
Parallel bus:
The parallel adapter board, plugs into JD8. The adapter board contains the
parallel control bus cable connectors.
X2
1
15
ST200 Cabinet
ST40-120 Cabinet
Содержание PowerWAVE 8000DPA RI (S2) Series
Страница 1: ...User Manual PowerWAVE 8000DPA ST S2 10 20 kVA kW Parallelable up to 400 kVA kW...
Страница 2: ...TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...
Страница 4: ...TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...
Страница 8: ...IV TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...