5: Operation
60
TS_616_08 PW8000DPA ST (S2) User Manual 21/4/22
5.3
Operating in ECO (on bypass) mode
When the UPS system is operated in ECO (on bypass) mode the load is powered from the UPS bypass mains supply, via
the static switch, under normal conditions and transfers to the inverter (on inverter mode) automatically if the bypass
mains supply fails.
5.3.1 How to power-up the UPS system and operate in ECO (on bypass) mode
1. To power-up the UPS system from a fully shut down condition, follow the standard UPS system start-up instructions in
paragraph 5.2 but do not perform the ‘
"Transfer the load to inverter"
2. On the module control panel, after 60s verify that:
a) The
LINE
1
LED is green.
b) The
LINE
2
LED changes to green.
c) The
BYPASS
LED is green.
d) The
INVERTER
LED is OFF.
e) The
BATTERY
LED is green.
f) The LCD displays
LOAD
NOT
PROTECTED.
5.3.2 How to transfer to ECO (on bypass) from on-line (on inverter) mode
The UPS can be manually switched to ECO (on bypass) from the on-line (on inverter) mode using the module control
panel load transfer menu.
1. On the module control panel (of any UPS module) press the
ENTER
key once to access the menu system.
2. Using the
UP/DOWN
keys, move the cursor so that it is adjacent to
COMMANDS
and then press the
ENTER
key.
3. Using the
UP/DOWN
keys, move the cursor so that it is adjacent to
LOAD
TO
BYPASS
and then press the
ENTER
key.
a) The UPS system will transfer the load to the static bypass (on all UPS modules).
4. On the module control panel(s), verify that:
a) The
INVERTER
LED is extinguished.
b) The
BYPASS
LED is green.
c) The LCD displays
LOAD NOT PROTECTED
.
CAUTION:
There will be a very short supply break when the UPS switches to the ‘on inverter’ mode, so you
should elect to operate the system in the ECO mode only if a load can withstand a brief power break.
CAUTION:
Before you carry out this procedure, warn the critical load user that the load will not be supplied with
processed, backed-up power once the transfer to maintenance bypass has been performed.
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
Содержание PowerWAVE 8000DPA RI (S2) Series
Страница 1: ...User Manual PowerWAVE 8000DPA ST S2 10 20 kVA kW Parallelable up to 400 kVA kW...
Страница 2: ...TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...
Страница 4: ...TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...
Страница 8: ...IV TS_616_08 PW8000DPA ST S2 UK User Manual 21 4 22...