9: Specification
78
TS_616_08 PW8000DPA ST (S2) User Manual 21/4/22
9.2
UPS Module characteristics
Mechanical
10 kVA UPS module
20 kVA UPS module
Dimensions (WxHxD)
(with front mounting wings)
mm
448 x 132 x 540 (3 HU)
488 x 132 x 540 (3 HU)
Weight UPS module
kg
18.6
21.5
Colours
Front: RAL 9005
Input characteristics
Output rated power per module cosφ 0.8
kVA
10
20
Output rated power per module cosφ 1.0
KW
10
20
Nominal input voltage
VAC
3x380/220V+N, 3x400V/230V+N, 3x415/240V+N
Input voltage tolerance
(ref to 3x400/230V) for loads in %:
VAC
(-20%/+15%) 3x320/184 V to 3x460/264 V for <100 % load
(-26%/+15%) 3x296/170 V to 3x460/264 V for < 80 % load
(-35%/+15%) 3x260/150 V to 3x460/264 V for < 60 % load
Input frequency
Hz
35 – 70
Input power factor
PF=0.99 @ 100% load
Inrush current
A
max. In
Input distortion THDI @ 100% load
< 4.5%
< 3.0
Max. input power with rated output power and charged
battery per module (output cosφ = 1.0)
kW
10.5
21
Max. input current with rated output power and charged
battery per module (output cosφ = 1.0)
A
15.2
30.4
Max. input power with rated output power and discharged
battery per module (output cosφ = 1.0)
kW
11.5
23
Max. input current with rated output power and
discharged battery per module (output cosφ = 1.0)
A
16.6
33.3
Output characteristics
Output rated power per module cosφ 0.8
kVA
10
20
Output rated power per module cosφ 1.0
KW
10
20
Output current in @ cosφ 1.0 (400 V)
A
14.5
29
Output rated voltage
VAC
3x380/220V or 3x400/230V or 3x415/240V
Output voltage stability
%
Static: < ±1%
Dynamic (Step load 0%-100% or 100%-0%) < ±4%
Output voltage distortion
%
With Linear Load< 1.5%
With Non-linear Load (EN62040-3:2001)< 3%
Output frequency
Hz
50 Hz or 60 Hz
Output frequency tolerance
%
Synchronized with mains < ±2%
(selectable for bypass operation) or < ±4%
Free /- 0.1%
Bypass operation
At Nominal Input voltage of 3x400 V ±15%
or 196 V to 264 V ph-N
Permissible unbalanced load
%
100% (All 3 phases regulated independently)
Phase angle tolerance
Deg.
2.0 deg. (With 100% unbalanced load)
Overload capability on inverter
%
125% load 10 min.
150% load 60 sec.
Output short capability (RMS)
A
Inverter: 3.0 x In during 40 ms
Bypass: 10 x In during 20 ms
Inverter: 2.25 x In during 40 ms
Bypass: 10 x In during 20 ms
Crest factor
3:1