TP-6126 8/02
A-61
Appendix
Ratings with Specific Manufacturers’ Circuit Breakers
Open- and Programmed-Transition Models
The following charts list power switching device withstand and closing ratings (WCR) in RMS symmetrical amperes for specific
manufacturers’ circuit breakers. Circuit breakers are supplied by the customer.
Switch
Molded-Case Circuit Breakers
Switch
Rating,
Amps
WCR, kA
RMS
Voltage,
Max.
Manufacturer
Type
Max. Size,
Amps
FH
80
Square D
FC, FI
100
q
KA, KC, KH, KI, LA, LH
250
TB1
100
GE
TEL, THED, THLC1, THLC2
150
TFL
225
CED6, ED6, HED4, HED6
125
70*
22
480
ITE
CFD6
150
70*
22
480
FD6, FXD6, HFD6
250
FCL, Tri-Pac FB
100
Cutler-Hammer
FD, FDC, HFD
150
Cutler-Hammer
HJD, JD, JDB, JDC
250
HKD, KD, KDB, KDC, LCL, Tri-Pac LA
400
ABB
S1
125
ABB
S3
150
Merlin Gerin
CE104, CE106
100
Square D
FC, FI
100
Square D
KA, KC, KH, KI, LA, LH
250
TB1
100
GE
TEL, THED, THLC1, THLC2
150
TFL
225
CED6, ED6, HED4, HED6
125
ITE
CFD6
150
104*
22
480
FD6, FXD6, HFD6
250
104*
22
480
FCL, Tri-Pac FB
100
Cutler-Hammer
FD, FDC, HFD
150
Cutler-Hammer
HJD, JD, JDB, JDC
250
HKD, KD, KDB, KDC, LCL, Tri-Pac LA
400
ABB
S1
125
ABB
S3
150
Merlin Gerin
CE104, CE106
100
Merlin Gerin
CF250
250
TEL, THED, THLC1
150
GE
TFL, THFK, THLC2
225
GE
SFL, SFP, TFJ, TFK
250
SGL4, SGP4, TLB4
400
CFD6, FD6, FXD6, HFD6
250
ITE
CJD6, HHJD6, HHJXD6, HJD6, JD6, JXD6, SCJD6, SHJD6,
SJD6
400
150*
22
480
KA, KC, KH, KI
250
150*
22
480
Square D
LC, LI
300
q
LA, LH
400
FD, FDC, HFD
150
Cutler-Hammer
HJD, JD, JDB, JDC
250
LCL, Tri-Pac LA, HKD, KD, KDB, KDC
400
ABB
S3
150
Merlin Gerin
CF250
250
Merlin Gerin
CJ400
400
* Open-transition models only
[
Programmed-transition models only
Содержание KCP MPAC 1000
Страница 22: ...TP 6126 8 02 12 Section 2 Installation ADV 6736 Figure 2 20 Interconnection Diagram...
Страница 75: ......