68
TP-6694
9/20
GenSet System
2.7.8
GenSet Calibration
This menu is only available in Decision-Maker
®
3000 controllers with firmware versions before 3.0.25. Go to Generator Metering
Menu
—Reset Calibration with controller firmware version 3.0.25 or higher.
Display provides access to the calibration factors for metering (volts and amps). Changing the system voltage or replacing the
main logic control circuit board requires calibration adjustment. Connect a meter with a minimum accuracy of 1% to the GenSet
output leads to calibrate the voltage-sensing logic.
The user can individually calibrate the values or reset all of them. The local display Reset all calib? No or Yes. Select No to
make no changes and exit GenSet Calibration. Select Yes to reset all of the values.
When calibrating voltage, the metered value and the number being entered as the calibrated value must be within 10% of the
system operating voltage.
When calibrating current, the metered value must be at least 25% of the rated current on units smaller than 100 kW and at least
50 amps on units rated larger than 100 kW. The number being entered as the calibrated value must within 10% of the metered
value.
GenSet - - > System
System Freq:
##.# Hz
System Volt:
###.# V
Pwr Rating:
##.# kW
Amp Rating:
##.# A
Power Type:
#####
Battery v:
## V
Meas System
English or Metric
Contrast
#####
AlarmSilence:
Always or Auto Only
Engine RPM
#####
User Selectable
(see manual speed
adjustment above) - >
SystemPhase:
#####
User Selectable - >
User Selectable - >
Содержание APM402
Страница 6: ...6 TP 6694 9 20 ...
Страница 16: ...16 TP 6694 9 20 ...
Страница 42: ...42 TP 6694 9 20 ...
Страница 78: ...78 TP 6694 9 20 ...
Страница 112: ...112 TP 6694 9 20 ...
Страница 120: ...120 TP 6694 9 20 ...
Страница 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Страница 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Страница 126: ...126 TP 6694 9 20 Figure 56 60 IMS 300 kW Wound Exciter Field 20 300 kW 600 V Perm Magnet Alternators ADV 5875AB 3 ...
Страница 127: ...TP 6694 9 20 127 Figure 57 300 kW and Larger Pilot Excited Permanent Magnet 4M 5M 7M 10M Alternators ADV 5875AB 4 ...
Страница 128: ...128 TP 6694 9 20 ...
Страница 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Страница 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Страница 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Страница 171: ......