TP-6137 5/03
46
Section 8 Controller Troubleshooting
4EOZ/3.5EFOZ Kohler generator
stopping operation.
The unit stops due to High
Cylinder Head Temperature
(HCHT) or High Exhaust
Temperature (HET) condition.
The operator stops the unit (local
or remote).
The unit stops due to a Low Oil
Pressure (LOP) condition.
The low oil pressure
deenergizes the relay (K2).
The high temperature contacts
deenergizes the relay (K2).
Push the ON/OFF switch.
The electric fuel pump (FP) and
the stop solenoid (FS) are
deenergized and the unit stops.
The electric fuel pump (FP) and
the stop solenoid (FS) are
deenergized and the unit stops.
The relay (K2) is deenergized.
Check the unit for causes of the
low oil pressure failure.
Check the unit for causes of the
high temperature failure.
The electric fuel pump (FP) and
the stop solenoid (FS) are
deenergized.
The unit stops. Release the
ON/OFF switch.
Figure 8-5
Stopping Operation
Содержание 3.5EFOZ
Страница 1: ...Marine Generator Sets Includes Engine Maintenance Models 4EOZ 3 5EFOZ TP 6137 5 03 Service ...
Страница 10: ...TP 6137 5 03 VI Safety Precautions and Instructions Notes ...
Страница 12: ...TP 6137 5 03 ii Service Assistance Notes ...
Страница 28: ...TP 6137 5 03 16 Section 3 Scheduled Maintenance Notes ...
Страница 42: ...TP 6137 5 03 30 Section 5 Fuel System Notes ...
Страница 48: ...TP 6137 5 03 36 Section 6 Cooling System Notes ...
Страница 102: ...TP 6137 5 03 90 Section 10 Generator and Engine Disassembly Reassembly Notes ...
Страница 104: ...TP 6137 5 03 92 Section 11 Wiring Diagrams 11 1 Wiring Diagram Schematic GM20645 B ...
Страница 105: ...TP 6137 5 03 93 Section 11 Wiring Diagrams 11 2 Wiring Diagram Point to Point GM20645 B ...
Страница 106: ...TP 6137 5 03 94 Section 11 Wiring Diagrams Notes ...
Страница 114: ......
Страница 115: ......