Section 3 Scheduled Maintenance
3.5 Generator Storage Procedure
Perform the following storage procedure before taking a
generator set out of service for three months or longer.
Follow the engine manufacturer’s recommendations, if
available,
for
fuel
system
and
internal
engine
component storage.
x:sm:002:001
3.5.1
Lubricating System
Prepare the engine lubricating system for storage as
follows:
1. Run the generator set for a minimum of 30 minutes
to bring it to normal operating temperature.
2. Stop the generator set.
3. With the engine still warm, drain the oil from the
crankcase.
4. Refill the crankcase with oil suited to the climate.
5. Run the generator set for two minutes to distribute
the clean oil.
6. Stop the generator set.
7. Check the oil level and adjust, if needed.
x:sm:002:002
3.5.2
Fuel System
Prepare the fuel system for storage as follows:
Diesel-Fueled Engines
1. Fill the fuel tank with #2 diesel fuel.
2. Condition
the
fuel
system
with
compatible
additives to control microbial growth.
See the
engine operation manual.
3. Change the fuel filter and bleed the fuel system.
See Section 5.
x:sm:002:004
3.5.3
Cooling System
Prepare the cooling system for storage as follows:
1. Unscrew the seawater pump cover to drain the
cooling water from the engine.
2. Remove the hose from the fitting to drain the
cooling water from the alternator.
3.5.4
Exterior
Prepare the exterior for storage as follows:
1. Clean the exterior surface of the generator set.
2. Seal all engine openings except for the air intake
with nonabsorbent adhesive tape.
3. To prevent impurities from entering the air intake
and to allow moisture to escape from the engine,
secure a cloth over the air intake.
4. Mask electrical connections.
5. Spread a light film of oil over unpainted metallic
surfaces to inhibit rust and corrosion.
x:sm:002:006a
3.5.5
Battery
Perform battery storage after all other storage
procedures.
1. Place the generator set master switch in the
OFF/RESET position.
2. Disconnect the battery(ies), negative (--) lead first.
3. Clean the battery.
4. Place the battery in a cool, dry location.
5. Connect the battery to a float/equalize battery
charger or charge it monthly with a trickle battery
charger.
Refer
to
the
battery
charger
manufacturer’s recommendations.
Maintain a full charge to extend battery life.
x:sm:002:007
Содержание 3.5EFOZ
Страница 1: ...Marine Generator Sets Includes Engine Maintenance Models 4EOZ 3 5EFOZ TP 6137 5 03 Service ...
Страница 10: ...TP 6137 5 03 VI Safety Precautions and Instructions Notes ...
Страница 12: ...TP 6137 5 03 ii Service Assistance Notes ...
Страница 28: ...TP 6137 5 03 16 Section 3 Scheduled Maintenance Notes ...
Страница 42: ...TP 6137 5 03 30 Section 5 Fuel System Notes ...
Страница 48: ...TP 6137 5 03 36 Section 6 Cooling System Notes ...
Страница 102: ...TP 6137 5 03 90 Section 10 Generator and Engine Disassembly Reassembly Notes ...
Страница 104: ...TP 6137 5 03 92 Section 11 Wiring Diagrams 11 1 Wiring Diagram Schematic GM20645 B ...
Страница 105: ...TP 6137 5 03 93 Section 11 Wiring Diagrams 11 2 Wiring Diagram Point to Point GM20645 B ...
Страница 106: ...TP 6137 5 03 94 Section 11 Wiring Diagrams Notes ...
Страница 114: ......
Страница 115: ......