MJ400306A1
27
(Some items are not shown on the meter.)
Set No.
Description
Initial
Set Value
Remarks
D-22
Flow rate OK judgment
range (%F.S.)
1.0
Settable range
:
0.5
~
100.0
D-26
Set flow rate tracking
function
00
00
:
Invalid
01
:
Valid
00
:
When setting a flow rate on
the indicator, the flow rate
will not be changed until the
[ENT] key is pressed.
D-27
PV filter (instantaneous
flow rate averaging)
02
00
:
No PV filter
01
:
Moving average of sampling 2
times
02
:
Moving average of sampling 4
times
03
:
Moving average of sampling 8
times
04
:
Moving average of sampling
16 times
05
:
Moving average of sampling
32 times
D-28
Indication update cycle
(indicator)
02
00
:
No update cycle
01
:
50-msec cycle
02
:
100-msec cycle
03
:
200-msec cycle
04
:
500-msec cycle
05
:
1000-msec cycle
D-29
0-2% range indication
setting
00
00
:
0-2
% flow rate indication
01
:
0
indication
01
:
Zero indication when a flow
rate is within 0±2
%
.
D-30
Full scale
※
Determined according to flow rates
Settable range
:
100
to
1000
Do not change these for normal
operations. If they are changed,
each SP value will be reset to
zero.
D-31
Position of decimal point
of full scale
※
00
:
Decimal point not used (
1000
)
01
:
Decimal point used (
100.0
)
02
:
Decimal point used (
10.00
)
03
:
Decimal point used (
1.000
)
※
The initial values are different depending on the specifications of the product.
Содержание 8700 MC
Страница 1: ...MJ400306A1 1 Thermal Mass Flow Meter Controller MODEL 8700 SERIES INSTRUCTION MANUAL...
Страница 33: ...MJ400306A1 33 19 External View 1 Integrated indicator type...
Страница 34: ...MJ400306A1 34...
Страница 35: ...MJ400306A1 35 2 Separate indicator type Main unit...
Страница 36: ...MJ400306A1 36...
Страница 37: ...MJ400306A1 37 Indicator URL http www kofloc co jp...