MJ400306A1
26
(Some items are not shown on the meter.)
Set No.
Description
Initial
Set Value
Remarks
D-13
Flow rate alarm setting
00
00
:
Not used
01
:
Only upper limit alarm used
02
:
Only lower limit alarm used
03
:
Upper/lower limit alarms used
When
“01 – 03”
are selected,
set
“D-14 – D-17”
at the
same time.
D-14
Selection of action when
flow rate alarm occurs
00
00
:
Control continue
01
:
Forced to fully closed
To cancel
“01: Forced to
fully closed”
, it is necessary
to change over the motion
modes such as “fully closed”
→”control” once.
D-15
Flow rate alarm upper
limit value (%F.S.)
10.0
Settable range
:
0.5
~
100.0
For Controller
100.0
Settable range
:
0.0
~
100.0
For Meter
D-16
Flow rate alarm lower
limit value (%F.S.)
10.0
Settable range
:
0.5
~
100.0
For Controller
0.0
Settable range
:
0.0
~
100.0
For Meter
D-17
Flow rate alarm delay
time (sec)
10.0
Settable range
:
0.5
to
999.9
D-18
Event output 1 type
selection
00
00
:
Not used (normally
0FF
)
01
:
0N
when integration flow rate
event occurs
02
:
0N
when flow rate is OK
03
:
0N
when operation mode =
Control
04
:
0N
when operation mode =
Fully opened
05
:
0N
when operation mode =
Fully closed
D-19
Event output 2 type
selection
D-20
Event output 1 delay
time (sec)
0.0
Settable range
:
0.0
to
999.9
D-21
Event output 2 delay
time (sec)
0.0
Settable range
:
0.0
to
999.9
Содержание 8700 MC
Страница 1: ...MJ400306A1 1 Thermal Mass Flow Meter Controller MODEL 8700 SERIES INSTRUCTION MANUAL...
Страница 33: ...MJ400306A1 33 19 External View 1 Integrated indicator type...
Страница 34: ...MJ400306A1 34...
Страница 35: ...MJ400306A1 35 2 Separate indicator type Main unit...
Страница 36: ...MJ400306A1 36...
Страница 37: ...MJ400306A1 37 Indicator URL http www kofloc co jp...