MJ400306A1
23
(3) Using the upper/lower limit alarms
(meter type)
Overview of the upper/lower limit alarm action:
When PV: instantaneous flow rate changes as time passes, the flow rate alarm is
judged.
ON
Flow rate alarm
OFF
AL. Hi
PV
Flow rate
Time
AL. dt
AL. dt
AL.Lo
0
①
②
AL. Hi : Flow rate alarm upper limit value
(
D-15
)
AL. Lo : Flow rate alarm lower limit value
(
D-16
)
AL. dt : Flow rate alarm delay time
(
D-17
)
PV : Instantaneous flow rate
①
Upper limit alarm
When the “PV value” exceeded the “AL. Hi”, the flow rate alarm is turned on after the
passage of “AL. dt”.
②
Lower limit alarm
When the “PV value” dropped below the “AL. Lo”, the flow rate alarm is turned on after
the passage of “AL. dt”.
※
For alarm codes, refer to 15. Alarm Codes and Corrective Actions.