Using the upper/lower limit alarms(controller type)
Overview of the upper/lower limit alarm action:
When PV: instantaneous flow rate (blue line) changes largely relative to SV: set flow
rate (green line) as time passes, the flow rate alarm is judged.
ON
流量アラーム
OFF
AL.Hi
SV
AL.Lo
流量
時間
AL.dt
AL.dt
AL. Hi : Flow rate alarm upper limit value
(
D-15
)
AL. Lo : Flow rate alarm lower limit value
(
D-16
)
AL. dt : Flow rate alarm delay time
(
D-17
)
SV : Set flow rate (green line)
PV : Instantaneous flow rate (blue line)
①
Upper limit alarm
When the “PV value” exceeded the “SV value + AL. Hi”, the flow rate alarm is turned
on after the passage of “AL. dt”.
②
Lower limit alarm
When the “PV value” dropped below the “SV value – AL. Lo”, the flow rate alarm is
turned on after the passage of “AL. dt”.
※
The above action is limited to the case where “00 : Control continue” has been
selected in “D-14 :Selection of action when flow rate alarm occurs”.
If “01 : Forced to fully closed” is selected, the valve fully closing action will start
when a flow rate alarm occurs. In this case, PV: Instantaneous flow rate is set to
zero, but the alarm indication and output continue.
Time
Flow rate alarm
Flow rate
Содержание 8700 MC
Страница 1: ...MJ400306A1 1 Thermal Mass Flow Meter Controller MODEL 8700 SERIES INSTRUCTION MANUAL...
Страница 33: ...MJ400306A1 33 19 External View 1 Integrated indicator type...
Страница 34: ...MJ400306A1 34...
Страница 35: ...MJ400306A1 35 2 Separate indicator type Main unit...
Страница 36: ...MJ400306A1 36...
Страница 37: ...MJ400306A1 37 Indicator URL http www kofloc co jp...