6. First Power Up and Commissioning

Once C35-VAV… has powered on a boot up screen will be displayed. The home screen, as 
shown on page 12 will appear once the device has finished booting up. The internal sensors 
require time to stabilize and power up. Only adjust offsets once the unit has had sufficient 
time (outlined below) to complete this process. Once the required time has elapsed compare 
sensors readings against a reference instrument. If required, the device can be calibrated using 
the Offsets menu instructions on page 25. 

6.1. Temperature measurement 

The C35-VAV… uses Internal Temperature Compensation (ITC) Algorithm to eliminate heat 
generated by internal electronic components. The ITC Algorithm requires up to 30 minutes to 
stabilize and achieve accurate temperature readings. Thermal resistance of surface on which 
the device is mounted will affect temperature readings. 

6.2. Relative humidity measurement 

Built-in humidity sensor (optional) utilizes temperature readings to calculate relative humidity. 
Allow 30 minutes for the device to calculate accurate readings of temperature and relative 
humidity prior to adjusting offsets. 

NOTE: If offset is added to temperature readings it will affect relative humidity readings. 

6.3. Carbon dioxide (CO

2

) measurement

The C35-VAV-C… uses Non-dispersive Infrared (NDIR) CO

2

 sensor to measure carbon dioxide 

concentration. The sensor uses automatic calibration procedure and it requires up to 7 days 
calibration. The calibration procedure keeps track of lowest CO

2

 concentration reading and 

uses that measurement as a default calibration point. The automatic calibration procedure is 
repeated on an ongoing (weekly) basis.

7. Touch screen operation and Maintenance

The C35-VAV… is primarily operated through its 3.5” resistive touch screen. 

The screen should not be operated with sharp objects which can scratch or damage the screen.

To clean the screen, simply wipe the front facing screen using a slightly damp cloth.

CAUTION

: Do not expose the device’s vents to liquids and do not use any cleaning agents on 

the device as this may result in sensor malfunction or incorrect readings.

8. Definitions

Term

Description

BACnet

A communication protocol for Building Automation and 
Control Networks

C35-VAV…

Configurable zone temperature, carbon dioxide and relative 
humidity controller for pressure depended or pressure 
independent VAV systems

Changeover

Change from heating to cooling or vice versa 

Control mode

The method used (Heating/Cooling) to bring the controlled 
zone to the target temperature

Control sequence

This parameter defines whether the HVAC system is capable of 
heating, cooling or heating and cooling, the controlled zone

CO

2

Carbon dioxide (measured in ppm)

Cooling / Heating Setpoints

The desired temperature range (°C)

Data Bus

RS485 physical layer standard for data transition

ECM

Electronically Commutated Motors. C35-VAV… is equipped 
with a 0-10v output for ECM fan control

HVAC

Heating Ventilation & Air Conditioning

Kd

Derivative gain for PID controller

Ki

Integral gain for PID controller

Kp

Proportional gain for PID controller

MS/TP

Master-Slave Token Passing

Offset 

The manual adjustment required to calibrate the temperature, 
CO

2

 or relative humidity, as measured by the sensor

PID controller

Proportional Integral Derivative controller

ppm

Parts per million

% rh 

Relative humidity (%)

RTD

Resistive Temperature Detector

Setpoints

The target value in a closed-loop feedback system

VAV

Variable Air Volume

Содержание C35-VAV...

Страница 1: ...C35 VAV Technical Manual Configurable zone temperature carbon dioxide and relative humidity controller for VAV systems and universal HVAC applications Firmware Version C35 VAV 1 0...

Страница 2: ...11 7 Sound On Off 11 8 About 12 Advanced Menu 12 1 Network 12 2 Security 12 3 Parameters 1 5 Main Configuration 12 4 Parameters 2 5 5 Air volume VAV Temperature PID and ECM 12 5 Offsets 12 6 Setpoint...

Страница 3: ...pied mode function Three operating modes Comfort Economy Standby Protection functionality in Standby mode Password protected menu and advanced menu Window contact or presence sensor input Automatic or...

Страница 4: ...ng conditions include inside facing walls which are in an open and central location of the unit s area of operation Warning In order to ensure accurate readings and correct operation the unit should n...

Страница 5: ...ll connections are in the correct terminals and that the correct voltage is being provided 3 Attach C35 VAV to the wall mount by sliding the unit onto the mounting brackets as shown in the diagrams be...

Страница 6: ...cedure is repeated on an ongoing weekly basis 7 Touch screen operation and Maintenance The C35 VAV is primarily operated through its 3 5 resistive touch screen The screen should not be operated with s...

Страница 7: ...ted or modified in the parameter screen a Save button will appear allowing users to save their changes If the Save button is not selected prior to changing screens any changes will not be saved and th...

Страница 8: ...an be adjusted in the setpoints menu 10 2 Economy mode 10 1 Comfort mode This mode prioritises user comfort and it is recommended that Comfort mode is activated only when the controlled zone is occupi...

Страница 9: ...mes The device will automatically manage the HVAC system to regulate temperature within the specific setpoints for each scheduled working mode Comfort Economy and Standby See page 17 for Scheduler set...

Страница 10: ...ase buttons on the home screen Once the required adjustments have been made select to save your changes 11 3 Setpoints Configuring Daily Scedules Once the week long schedule has been set the daily pro...

Страница 11: ...e to the total number of devices on the data bus Max Info Frames The maxium number of requests a device is able to send over the local network For optimal network performance this value should be set...

Страница 12: ...n operates only when Heating is active and according to the ambient temperature the lower the ambient temperature the higher the fan speed Parallel with heat exchanger VAV damper actuator will be cont...

Страница 13: ...FF voltage to value that will turn off the ECM fan ECM MIN voltage Defines the minimum signal value and the minimum speed of the fan 5 ECM MAX voltage Defines the maximum signal value and the maximum...

Страница 14: ...een closed the system will resume normal operation If the Presence sensor parameter is selected and presence sensor is not detecting any presence the system will go from Comfortable mode to Economy mo...

Страница 15: ...0 V T1 Floor temperature sensor Pt1000 Q1 Remote air quality sensor 0 10 V 0 2000ppm Main configuration Control sequence Heating only Cooling and heating Cooling heating coil Enabled Fan operating mod...

Страница 16: ...lve actuator DC 0 10V cooling S1 Switch for window contact or presence sensor C1 BACnet MS TP bus connection C35 VAV with VAV damper actuator heating or cooling coil and ECM fan D1 Zone controller C35...

Страница 17: ...ow Maintain same polarity between devices on a single power supply 17 3 Maximum number of devices on data bus The C35 VAV B RS is categorized as BACnet MS TP Master device The maximum number of Master...

Страница 18: ...0 ppm 3 of measured value Step response time 90 3 minutes Sampling intervals 5 seconds Warming up time 3 minutes Calibration time 7 Days Display Type Graphical TFT LCD Touchscreen type Resistive singl...

Страница 19: ...ce instrument Codis has not had enough time to power up and stabilize Read chapter First start up and Commissioning Relative humidity reading is incorrect The device has not been calibrated Calculate...

Страница 20: ...ssary The device does not communicate over the BACnet MS TP network Count the number of devices on the network segment The maximum number of devices on a network segment has been exceeded Install a BA...

Страница 21: ...ER Product Name C35 VAV Product Model Number C35 VAV B RS G Application Software Version unknown Firmware Revision unknown BACnet Protocol Revision 14 Product Description C35 VAV is a configurable zon...

Страница 22: ...Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium __________ BACnet ZigBee ANNEX O Other Device Address Binding Is static device binding supported This is currently necessary for tw...

Страница 23: ......

Отзывы: