Koer C35-VAV... Скачать руководство пользователя страница 3

4

C35-VAV

5

C35-VAV

1. Introduction

Thank you for purchasing a KOER product. KOER is a brand dedicated to the development and 
production of the next generation of hardware and software solutions for HVAC management 
and building automation systems. Our vision is to continuously develop and produce quality 
products for the building automation industry which will have a positive impact on user 
environments, quality of life and, health and safety. With this in mind, we value any insights or 
feedback you may have regarding our products. (Email: [email protected])

1.1. Use

This device (C35-VAV…) can be used for temperature, air quality and humidity control of 
individual zones as part of a Demand Controlled Ventilation system, HVAC system or as a 
standalone controller. 

C35-VAV… can be used in HVAC systems for:

Heating

Cooling

Ventilation

Dehumidification

C35-VAV… can control of the following operational elements:

Damper actuators

Heat exchange actuators

Radiator/Floor heating actuator

Modulating electric heaters

EC motor fan

1.2. Hardware features

Main hardware features include:

Resistive Color TFT touchscreen display

Built-in sensors:
- Temperature
- CO

2

 (optional)

- Relative Humidity (optional)

Three analog 0…10 V DC outputs

One analog 0…10 V DC input

One analog resistive input

One binary input

RS-485 transceiver (optional)

Galvanic isolated RS-485 transceiver (optional)

Real Time Clock

Easy wall mounting

Power supply 24 V AC/DC

1.3. Software features

PID control based on temperature, air quality and humidity parameters

Weekly scheduler, four preset modes, up to eight scheduler timers per day

Occupied mode function

Three operating modes: Comfort, Economy, Standby

Protection functionality in Standby mode

Password protected menu and advanced menu

Window contact or presence sensor input

Automatic or manual changeover

Standby, Dim and Night Mode display brightness

Easily configurable commissioning and working parameters

Setpoint limitations for users

BACnet MS/TP communication protocol (optional)

Internal Temperature Compensation Algorithm

Factory Reset function

1.4. Applications

The C35-VAV… was designed for the following VAV applications:

Single duct

Single duct with electric heater

Single duct and radiator

Single duct with heating and/or cooling coil

Pressure independent VAV applications:

Single duct with serial fan

Single duct with parallel fan

Single duct with serial fan and heating or cooling coil

Single duct with parallel fan and heating or cooling coil

1.5. Type Summary & Ordering Info

Product 
Summary

Inputs

Outputs

Built in Sensors

Protocol Network Interface Enclosure color

0-10V Pt1000 Binary 3x0-10V Temp. Humidity

CO

2

BACnet

RS485 Isolated 

rs-485

White

Black

Option 
Codes

-H

-C

-B

/RS

/RS-G

-BLK

C35-VAV

O

O

O

O

O

O

√ - Available
O - Option

Ordering Code

E.g. C35-VAV-C-B/RS-G

Naming 
Convention

1) Device

2) Application

3) Options

4) Network Interface

5) Enclosure color

C35

VAV

C = CO

2

 sensor

Isolated RS485

White

2. Before use or installation

It is strongly recommended that installation is performed by a qualified professional and 
that this user manual is read carefully prior to installation. Incorrect installation may result 
in malfunction, damaging the device or incorrect configuration. Please ensure you have the 
correct user manual for the firmware version as shown on the ‘About’ screen (see page 20). 
This manual was specifically written for 

Firmware Version C35-VAV 1.0

.

Содержание C35-VAV...

Страница 1: ...C35 VAV Technical Manual Configurable zone temperature carbon dioxide and relative humidity controller for VAV systems and universal HVAC applications Firmware Version C35 VAV 1 0...

Страница 2: ...11 7 Sound On Off 11 8 About 12 Advanced Menu 12 1 Network 12 2 Security 12 3 Parameters 1 5 Main Configuration 12 4 Parameters 2 5 5 Air volume VAV Temperature PID and ECM 12 5 Offsets 12 6 Setpoint...

Страница 3: ...pied mode function Three operating modes Comfort Economy Standby Protection functionality in Standby mode Password protected menu and advanced menu Window contact or presence sensor input Automatic or...

Страница 4: ...ng conditions include inside facing walls which are in an open and central location of the unit s area of operation Warning In order to ensure accurate readings and correct operation the unit should n...

Страница 5: ...ll connections are in the correct terminals and that the correct voltage is being provided 3 Attach C35 VAV to the wall mount by sliding the unit onto the mounting brackets as shown in the diagrams be...

Страница 6: ...cedure is repeated on an ongoing weekly basis 7 Touch screen operation and Maintenance The C35 VAV is primarily operated through its 3 5 resistive touch screen The screen should not be operated with s...

Страница 7: ...ted or modified in the parameter screen a Save button will appear allowing users to save their changes If the Save button is not selected prior to changing screens any changes will not be saved and th...

Страница 8: ...an be adjusted in the setpoints menu 10 2 Economy mode 10 1 Comfort mode This mode prioritises user comfort and it is recommended that Comfort mode is activated only when the controlled zone is occupi...

Страница 9: ...mes The device will automatically manage the HVAC system to regulate temperature within the specific setpoints for each scheduled working mode Comfort Economy and Standby See page 17 for Scheduler set...

Страница 10: ...ase buttons on the home screen Once the required adjustments have been made select to save your changes 11 3 Setpoints Configuring Daily Scedules Once the week long schedule has been set the daily pro...

Страница 11: ...e to the total number of devices on the data bus Max Info Frames The maxium number of requests a device is able to send over the local network For optimal network performance this value should be set...

Страница 12: ...n operates only when Heating is active and according to the ambient temperature the lower the ambient temperature the higher the fan speed Parallel with heat exchanger VAV damper actuator will be cont...

Страница 13: ...FF voltage to value that will turn off the ECM fan ECM MIN voltage Defines the minimum signal value and the minimum speed of the fan 5 ECM MAX voltage Defines the maximum signal value and the maximum...

Страница 14: ...een closed the system will resume normal operation If the Presence sensor parameter is selected and presence sensor is not detecting any presence the system will go from Comfortable mode to Economy mo...

Страница 15: ...0 V T1 Floor temperature sensor Pt1000 Q1 Remote air quality sensor 0 10 V 0 2000ppm Main configuration Control sequence Heating only Cooling and heating Cooling heating coil Enabled Fan operating mod...

Страница 16: ...lve actuator DC 0 10V cooling S1 Switch for window contact or presence sensor C1 BACnet MS TP bus connection C35 VAV with VAV damper actuator heating or cooling coil and ECM fan D1 Zone controller C35...

Страница 17: ...ow Maintain same polarity between devices on a single power supply 17 3 Maximum number of devices on data bus The C35 VAV B RS is categorized as BACnet MS TP Master device The maximum number of Master...

Страница 18: ...0 ppm 3 of measured value Step response time 90 3 minutes Sampling intervals 5 seconds Warming up time 3 minutes Calibration time 7 Days Display Type Graphical TFT LCD Touchscreen type Resistive singl...

Страница 19: ...ce instrument Codis has not had enough time to power up and stabilize Read chapter First start up and Commissioning Relative humidity reading is incorrect The device has not been calibrated Calculate...

Страница 20: ...ssary The device does not communicate over the BACnet MS TP network Count the number of devices on the network segment The maximum number of devices on a network segment has been exceeded Install a BA...

Страница 21: ...ER Product Name C35 VAV Product Model Number C35 VAV B RS G Application Software Version unknown Firmware Revision unknown BACnet Protocol Revision 14 Product Description C35 VAV is a configurable zon...

Страница 22: ...Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium __________ BACnet ZigBee ANNEX O Other Device Address Binding Is static device binding supported This is currently necessary for tw...

Страница 23: ......

Отзывы: